Fault code is shown as
27 and the icon
is
lighting on LCD display
and alarm is
continuously sounding.
Battery voltage is too high or
the charger is fault.
Contact Atlantis SpA.
Fault code is shown as
28 and the icon
is
lighting on LCD display
and alarm is
continuously sounding.
Battery voltage is too low or
the charger is fault.
Contact Atlantis SpA.
The icon
and the
icon
are
flashing on LCD display
and alarm is sounding
twice every second.
UPS is overload
Remove excess loads
from UPS output.
Fault code is shown as
43 and The icon
is
lighting on LCD display
and alarm is
continuously sounding.
The UPS shut down
automatically because of
overload at the UPS output.
Remove excess loads
from UPS output and
restart it.
Fault code is shown as
14 and alarm is
continuously sounding.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.