105
A03-OP3001-RC
Battery Low
67.68V -69.12V± 1%
Battery CutOFF
60.12V -67.68V± 1%
Battery Charging Voltage
82,1VDC ±1%
Charging Current (max)
1.5A
Voltage Range (Online Mode)
Vin(V)
Action
Vout(V)
Note
Vin
≦
160 ± 3%
Switch to Battery
Mode
INV Battery (220±
1%)
the UPS returns to
AC output mode
when AC input
increase to 175V
(3%)
166V
≦
Vin
≦
300V
Online Mode
INV AC (220± 1%)
Vin
≧
300± 5%
Switch to Battery
Mode
INV Battery (220±
1%)
The UPS returns to
AC output mode
when AC input drops
to 290V (3%)
Voltage Range (x ECO Mode)
Vin(V)
Action
Vout(V)
Note
Vin
≦
LS
Switch to Battery
Mode
INV Battery (220±
1%)
Vout : - 7Vac
<LS<
Vout -24 Vac
LS
≦
Vin
≦
HS
ECO Mode
Vout=Vin
Vin
≧
HS
Switch to Battery
Mode
INV Battery (220±
1%)
Vout : + 7Vac
<HS<
Vout +24 Vac