Atlantis Solar Air Conditioner Installation
Notice:
①
When the pipe line is extended, discharge the air in the connecting pipe with
refrigerant gas, which is from the outside of the system. And then, discharge the
redundant refrigerant in degassing method.
②
Installation height of the indoor unit and the outdoor unit should be below 5 m.
③
The length of the pipe, which connects the indoor unit and the outdoor unit, should be
less than 10 m.
④
The refrigerant filling amount of the Atlantis Solar Air conditioner should be adjusted
according to the length of the pipe (L). The refrigerant increment G= (L- length of the
standard pipe)*80(g/m).
Connection of the Power Supply of the Outdoor Units
Dismount the outlet box of the outdoor unit; connect the triple core wire and the twin core
wire with the five jacks of the connecting terminals in accordance with their colors. As
shown in the following form, the connection method of the triple core wire of the subsidiary
electric heating pipe on the insulating barrel is that the blue wire is connected with terminal
board 4 (N), the red wire is connected with terminal board 3; the yellow/green wires are
connected with terminal board grounded.
The Terminal Board Base on the
Outdoor Units
1
2
3
4(N)
The Color of Wire Connected With
the Indoor Unit
Brown Black
Red
Blue
Yellow/Green
Connecting with the Auxiliary
Electric Heating Tank
Red
Blue
Yellow/Green