13
BOILER ELECTRICAL PROTECTION
Selection of fuses
Fuses F1, F2 & F3 - cartridge size 8.5 x 31.5
90kW to 280kW
F1 - 1A type aM
F2 - 1A type gG
F3 - 0.5A type gG
315kW to 630kW
F1 - 1A type aM
F2 - 2A type gG
F3 - 0.5A type gG
Fuses F4, F5 & F6
Cartridge size 22 x 58 - 63A type gG
Miniature circuit breakers
output - 0 - 125A type gG
output - 1 - 160A
type gG
output - 2 - 250, 315 & 400A type gG
Selection of FUSES or CIRCUIT BREAKERS
Boiler
output
F4
F5
F6
Boiler
output
F4
F5
F6
90 kW
63 A
63 A
63 A
385 kW
250 A
250 A
160 A
120 kW
125 A
63 A
63 A
420 kW
250 A
250 A
250 A
150 kW
125 A
125 A
63 A
455 kW
315 A
250 A
250 A
180 kW
125 A
125 A
125 A
490 kW
315 A
315 A
250 A
210 kW
125 A
125 A
125 A
525 kW
315 A
315 A
315 A
245 kW
160 A
125 A
125 A
560 kW
400 A
315 A
315 A
280 kW
160 A
160 A
125 A
595 kW
400 A
400 A
315 A
315 kW
160 A
160 A
160 A
630 kW
400 A
400 A
400 A
350 kW
250 A
160 A
160 A