EN
42
4.2 Connection with a temperature limiter
4.3 Connecting to a pressure reducer
The pressure reducer is mandatory if the water pressure in your home is greater than 0.5 MPa (5 bar).
Place it on the cold water inlet, to your water meter outlet, never directly to the water heater.
4.4 Filling the water heater
u
Turn on the house’s HOT water taps.
v
Turn on the cold water valve located on the safety unit.
w
The water heater is filled as soon as you notice a flow of cold
water at the hot water valve outlet. Close these.
x
Check that the safety unit is operating correctly by moving the
drain valve. A little water should flow out.
y
Check the sealing at the water inlet and outlets on the water heater.
If you notice a leak, try to retighten the connections.
If the leak persists, drain the water heater (see page 44) and retighten the
connections.
Start the operation again until full sealing is achieved.
Filling:
10 litres
a minute
NO
Cold water
take-off
Inlet mains
cold water
Évacuation
des eaux
usées
Réducteur
de pression
NO
Groupe de sécurité
Piquage
eau froide
Arrivée
eau froide
du réseau
Piquage
eau froide
Arrivée
eau froide
du réseau
YES
Le réducteur
de pression ne doit
pas être raccordé
directement sur le
chauffe-eau
Waste water
drainage (drains)
Ingang
waterleiding
Watermeter
Algemene kraan
bij ingang van koud water
Pressure
reducer
Safety unit
È
È
0000000
Algemeen installatieschema
Voorbeeld met een verticale muurboiler
Hot water
outlet
Cold water
inlet
Siphon
Dielectric
connection
Temperatuur
-begrenzer
Fase
Aarde
Neutraal
Koud water
Warm water
È
È
Elektrisch schema
Zekering 16 A, contacts-
chakelaar dag/nacht
en differentieelschakelaar
30 mA
Kraan in bijvoorbeeld
een badkamer
Water inlet mains
È
Installation Manual: Water heater water connections
Temp.
limiter
Dielectric
connection
Siphon
Unit
safety
MANDATORY
ESSENTIAL
Cold water
Hot water
Mixed water
New and renovated
(decree of 30/11/2005)
For pipes made from PER
Must withstand
100° C and 10 bar
If your pipes are made from synthetic materials
(plastic or PER for example), it is essential to fit
a temperature limiter (or thermostatic regulator).
The limiter must never be connected directly
to the water heater.
The temperature limiter enables the risks
of burning to be limited.
Содержание CHAUFFEO
Страница 30: ......
Страница 34: ......
Страница 58: ......
Страница 86: ...U0695761 A 4 février 2021 2 45 PM 84 ...