Heating cable (optional)
-Locate the heating part (see
fig. 33
).
-Place the thermostat at the bottom of the tank.
-Run the bottom of the tank with the heating part of the
cable (make sure that the drain hole is covered by the
heating part).
-Fix the heating part on the bottom of the tank with the
aluminum tape supplied.
-Route the cable to the terminal block away from the
propeller blades (use the attachment points with clamps).
Avoid metal edges that could damage the
insulation.
-Connect the heating cable to the terminal block
(terminals L and N).
fig. 33 -
Heating cable mounting
Thermostat
Repère
Partie chauffante
1 m
Partie froide
Alimentation
1.5 m
L1 L2 L3 N 1 2 3
POWER INDOOR UNIT
N
L
Thermostat
mark
Heating part
1 m
Cold part
Supply
1.5 m
Interconnection
cable
Main electricity
supply
Heating cable
- 37 -