Circuit Board Division
800.261.3602
16
Revised 02/21
GSCM-mini-P Westinghouse Model # WGen9500DF & Samlex Inverter
Wires to the Remote/ATS connector
The GSCM-mini-P uses the generator’s Remote/ATS connector for all connections to the generator. The GSCM-mini-P’s
power, relay and run feedback connections us the ATS connector as shown above. The generators engine switch is left in the
ON position. This allows the GSCM-mini-P to start and stop the generator without an additional control relay. A battery
tender/charger is used to keep the battery from discharging due to the engine switch being left on 24/7.
The GSCM-mini-P’s terminal #6 is connected to terminal #3 (+12vdc) and to Samlex’s normally open relay contact, and the
common contact wires back to terminal #5 on the GSCM-mini-P. The generators DC output is wired to terminals # 7 & 8
providing the run feedback signal. An optional Battery tender/charger is not needed for this option.
The GSCM-mini-P accepts Samlex’s two wire relay contact (maintained run signal) and provides a one second start /stop pulse
as outlined on page 6 GSCM-mini-P opion#2.