Atkinson Electronics GSCM-mini-P Скачать руководство пользователя страница 13

www.atkinsonelectronics.com

 

 

 

                                                    

Circuit Board Division 
800.261.3602 

13 

Revised 02/21

 

GSCM-mini-P                             Cummins/Onan P9500DF generator & Samlex Inverter 

Wires to the Remote/ATS connector 

 

 

 
 
The GSCM-mini-P uses the generator’s Remote/ATS connector for all connections to the generator.  The GSCM-mini-P’s 
power, relay and run feedback connections us the ATS connector as shown above.  A control C1 relay is wired in series with 
the ground wire  to break the ground connection running to the engine switch terminal #5.  The C1 relay connects as follows 
terminals 86 and 30 connect to ground, terminal 85 connects to engine switch terminal #1 and terminal 87a connects to 
engine switch #5.  Engine switch to be left in the OFF position.  
 
The GSCM-mini-P’s terminal #6 is connected to terminal #3 (+12vdc) and to Samlexs’s normally open relay contact, and the 
common contact wires back to terminal #5 on the GSCM-mini-P. The generators DC output is wired to terminals # 7 & 8 
providing the run feedback signal. An optional Battery tender/charger is not needed for this option. 
 
The GSCM-mini-P accepts Samlex’s two wire relay contact (maintained run signal) and provides a one second start /stop pulse 
as outlined on page 6 GSCM-mini-P opion#2. 
 
If a battery tender/charger is used, the engine switch should be left in the ON position and the C1 control relay is not used. 

 
 

Содержание GSCM-mini-P

Страница 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Страница 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Страница 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Страница 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Страница 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Страница 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Страница 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Страница 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Страница 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Страница 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Страница 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Страница 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Страница 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Страница 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Страница 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Страница 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Страница 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Страница 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...

Отзывы: