ENG - Manual of installation, use and maintenance.
210-0352_libretto_WHC_ATI_eng.docx
24
Jan-19
MENU 02 - "SETTINGS" RESERVED TO THE INSTALLER
Index
Description
Default
Range
Unit of
measurement
01
Δ
T (+ temperature offset) respect to storage set-point for the burner
turning off
0
[0-5]
° C
02
ΔT (
- temperature offset) respect to storage set-point for the burner
ignition
3
[1 - 15]
° C
03
ΔT
(+ temperature offset) respect to the outgoing set-point for the burner
turning off
5
[1-5]
° C
04
Δ
T (- temperature offset) respect to the outgoing set-point for the burner
ignition
4
[1-5]
° C
05
Maximum value for storage set point
60
[55-65]
° C
06
Minimum value for storage set point
40
[40-50]
° C
07
Outgoing storage set-point (+ offset respect to the storage set-point).
3
[0-5]
° C
08
Limit temperature for the tank sensor
85
[65-85]
° C
09
Limit Temperature for the flue gas probe
100
[80-110]
° C
10
Maximum increase at the outgoing probe
8
[4-16]
° C
11
Increase range for outgoing probe
2
[1-5]
Seconds
12
Control limit at outgoing probe increase
60
[40-80]
° C
13
LCD backlighting
1
[0-2]
-
14
Circulator modulation Offset "+"
4
[0-10]
%
15
Circulator modulation Offset "-"
(-) 4
[0 - (-) 10]
%
16
Update time pump modulation offset
1
[0-2]
Seconds