ATI
Q46C2 2Electode Conductivity System
Part 4
– Electrical Installation
17
O&M Manual
Rev-H (6/19)
4.3
Relay Connection
Three SPDT relays are provided on the power supply board. None of the relay contacts are
powered. The user must supply the proper power to the contacts. For applications that require the
same switched operating voltage as the Q46 (115 or 230 V), power may be jumpered from the
power input terminals at
TB7.
Relay wiring is connected at
TB4, TB5, and TB6
as shown below.
Note that the relay contact markings are shown in the NORMAL mode. Programming a relay for
“Failsafe” operation reverses the NO and NC positions as shown in diagram below.
Figure 9 - Relay Connections