ATI
MetriNet Ethernet/IP Communications Manual
27
O&M Manual
Rev-A (6/19)
***No supported services or attributes***
1.10 Optional Tool Examples: RSLinx Classic
The primary method of setup for the MetriNet at this time is a Genetic Module” and
is simply entered into most PLCs using the I/O settings found in section 1.8. Those
main T->0 and O->T settings are then byte parsed into the needed final values.
The EDS file if often not even needed for this type of installation.
A brief setup with RSLinx Classic using an OPC server is shown next, which will
verify operation of the interface. While these screenshots are specific to Rockwell
tools, the same set-up steps are part of other platforms that support Ethernet/IP.
RSLinx Classic is chosen here as its very common for Ethernet/IP, and it is the
foundation communication driver component for RSLogix Studio 5000. In addition,
using the OPC server function allows all of this testing to be done without a PLC.
This all runs on a single computer, with only the MetriNet connected to the PC
Ethernet port. So, this test can also be used as a quick field test of Ethernet/IP
adapter devices off the main network.
Before running this step, confirm that –
1-The proper EDS file has been properly loaded.
2-The MetriNet has already been configured with the proper IP address to
match the network requirements. Turn on MetriNet but do not connect
it to PC port yet.
3-For RSLinx Classic, this example assumes the user has a version other
than the “Lite” version, as that version does not allow an OPC server
connection. The “single node”, “OEM”, and “gateway” versions all can
run an OPC server.