MetriNet Ethernet/IP Communications Manual
14
O&M Manual
Rev-A (6/19)
Identity Instance Common Services
Service Code
Implemented for
Service Name
Class Level
Instance Level
05
HEX
No
Yes
Reset
0E
HEX
Yes
Yes
Get_Attribute_Single
Input Assembly Object (04
HEX
– 1 Instance)
The Input Assembly Object is a collection of all the measurement information that
can be read from the MetriNet. This includes all data from any attached sensor(s.)
This is “read only” data that the MetriNet can send out. The data arrangement is
detailed below, including the byte size of various data fields.
Class Attributes (Instance 0)
Attribute ID
Name
Data Type
Data Value
Access Rule
1
Revision
UINT
2
Get
2
Max Instance
UINT
0x66 (102 decimal)
Get
Input Instance Attributes (Instance 101)
Attribute ID
Name
Data Type
Default Data Value
Access Rule
3
Input Data
VARIES
0
Get
Input Instance Common Services
Service Code
Implemented for
Service Name
Class Level
Instance
Level
0E
HEX
Yes
Yes
Get_Attribute_Single
Input Instance 101 – 500 Bytes
System IINFO
Bytes
Data Type
Description
0–1
WORD
Interface Status Flags
1
2–3
WORD
System Status 1 Flags
2
4–5
WORD
System Status 2 Flags
2
6–7
UINT
Number of Sensors
8–9
UINT
IP Address High
10–11
UINT
IP Address Low
12–13
UINT
Subnet Mask High
14–15
UINT
Subnet Mask Low
16–17
UINT
Gateway High
18–19
UINT
Gateway Low