background image

GasSens

 Gas Detection System 

                     Sec

tion 4 - Optional Equipment

 

 

O & M Manual 
A14-RK, 8/06 

 

                 4 

 

Electrical  connection  is  made  between  the  battery  back-up  unit  and  the  power  supply  module.    The 

circuit board mounted on the battery contains a 2 position plug-in terminal block marked plus and minus.  
The plus terminal is connected to terminal B+ of the power supply and the minus terminal is connected to 
B- of the power supply.   
 

 

Operation 

 

When  power  is  applied  to  the  power  supply  module,  a  relay  on  the  battery  back-up  circuit  board 

energizes  and  places  the  battery  back-up  into  operation.    There  are  no  user  adjustments  in  the  battery 
back-up unit.  If the battery is not fully charged, the power supply will begin supplying charge current to the 
battery, and will float charge the battery as long as the power supply is on.   

 
Should  the  power  supply  loose  its  input  power,  the  battery back-up will immediately supply power to 

receiver modules to maintain detection system operation without interruption.  The back-up period will vary 
depending on whether the detector is single channel or two channel, on whether displays are in normal or 
high intensity mode, and on how many relays are configured for fail-safe operation.  The minimum period 
expected for a single channel system is 12 hours and for a two channel system is 6 hours.  Normally, the 
back-up period is twice as long as the minimums. 

 
The circuit board attached to the battery serves two functions.  First, it regulates the charging current 

to  the  battery  to  a  maximum  of  0.75  amps.    This  prevents  possible  damage  to  the  battery  due  to  an 
excessively  high  charge  current.    Second,  it  isolates  the  battery  from  the  detection  system  when  the 
battery voltage falls below 10 volts.  This is done through a relay, and protects the battery against damage 
caused by very deep discharge. 

 
The  isolation  relay  that  protects  against  deep  discharge  will  also  protect  the  battery  against  an 

external  short  circuit  of  the  wires  connected  to  the  battery.    If  a  short  occurs,  the  relay  will  immediately 
open, protecting the battery and limiting the current that the battery will deliver.   

 

 

Removal from Service 

 

The relay that isolates the battery when the 10 volt level is reached is energized as soon as power is 

applied  to  the  power  supply  module.    Once  energized,  the  coil  current  is  supplied  from  the  battery  if 
needed.    If the gas detection system supported by the battery back-up is started up for testing and then 
shut  down,  the  battery  back-up  relay  should  be  de-energized  manually.    Otherwise,  the  relay  coil  will 
continue  to  draw  power  from  the  battery  until  the  10  volt  level  is  reached.    While  this  will  not  cause 
damage, it means that the battery will be discharged when the detection system is started up again.   

 
To de-energize the relay, slide the control circuit board off the battery terminals briefly and then slide it 

back  on.    As  soon  as  the  battery  connection  is  broken,  the  relay  coil  will  drop  out,  and  will  not  energize 
until  power  is  applied  to  the  power  supply  module  in  the  system.    This  procedure  is  recommended  any 
time the detection system is to be shut down for more that a few days. 
 

Содержание GasSens

Страница 1: ...ogy Inc ATI UK Limited 6 Iron Bridge Drive Unit 1 2 Gatehead Business Park Collegeville PA 19426 Delph New Road Delph Phone 800 959 0299 Saddleworth OL3 5DE 610 917 0991 Phone 44 0 1457 873 318 Fax 61...

Страница 2: ...Y CONFIGURATION 2 3 CONFIGURATION SWITCHES 2 3 SETPOINT SELECTION 2 5 RANGE SELECTION 2 6 RELAY CONFIGURATION 2 6 EXTERNAL HORN RELAY 2 7 DISPLAY INTENSITY 2 7 OPERATION 2 8 STARTUP 2 8 ALARM ACKNOWLE...

Страница 3: ...GasSens Gas Detection System Section 1 Overview O M Manual A14 RK 8 06 1 2 BATTERY BACKUP PARTS LIST 4 3 STROBE PARTS LIST 4 3 STROBE LIGHT 4 3...

Страница 4: ...ine Dioxide 12 0 2 PPM 0 1 PPM 0 100 PPM Fluorine 13 0 2 PPM 0 1 PPM 0 100 PPM Hydrogen Peroxide 34 0 10 PPM 0 10 PPM 0 100 PPM Ozone 14 0 2 PPM 0 1 PPM 0 100 PPM Iodine 35 0 2 PPM 0 1 PPM 0 100 PPM A...

Страница 5: ...isual indication of alarm status A17 Power Supply Module Provides 12 VDC power to one or two receiver modules plus power for an audible horn and for charging an external battery Packaged in the same c...

Страница 6: ...odule Mounting is by 1 2 MNPT nipple making it convenient to mount directly to a NEMA enclosure A19 Battery Back up Provides a 12 VDC 4 AH battery and charging control circuitry in a separate NEMA 4X...

Страница 7: ...ngs of the one two three and six module enclosures Each enclosure is supplied with conduit hubs for connection of 1 2 NPT threaded conduit Also included is a seal ring for each hub Seal rings are requ...

Страница 8: ...ic cable glands are available from most electrical supply stores Gland seals with 1 2 NPT threads will screw directly into the conduit hub Gland seals are also available from ATI for installation dire...

Страница 9: ...ns Gas Detection System Section 1 Overview O M Manual A14 RK 8 06 1 8 THRU HOLES FOR SURFACE MOUNTING 4 6 SCREWS SIDE VIEW FRONT VIEW BOTTOM VIEW Figure 1 2 Two Module System Enclosure Dimensions 80 0...

Страница 10: ...s Gas Detection System Section 1 Overview O M Manual A14 RK 8 06 1 9 THRU HOLES FOR SURFACE MOUNTING 4 6 SCREWS SIDE VIEW FRONT VIEW BOTTOM VIEW Figure 1 3 Three Module System Enclosure Dimensions 80...

Страница 11: ...GasSens Gas Detection System Section 1 Overview O M Manual A14 RK 8 06 1 10 Figure 1 4 Six Module System Enclosure Dimensions 80 0008R...

Страница 12: ...quired Single point detection systems are supplied with the power supply receiver and optional horn factory wired as shown in Figure 1 5 below Analytical Technology Inc Figure 1 5 Single Point Receive...

Страница 13: ...iew O M Manual A14 RK 8 06 1 12 Two point detectors include one power supply and two receivers These systems are shipped factory wired as shown in Figure 1 6 below Analytical Technology Inc Figure 1 6...

Страница 14: ...GasSens Gas Detection System Section 1 Overview O M Manual A14 RK 8 06 1 13 Analytical Technology Inc Analytical Technology Inc Figure 1 7 Four Point Receiver Internal Wiring ATI 075...

Страница 15: ...ems supplied in Large type enclosures use a 65 watt power supply located in the top of the enclosure This power supply is designed to power up to 12 of the A14 receiver modules Figure 1 8 shows typica...

Страница 16: ...connected properly Sensor transmitters supplied with the generator from the factory will be factory wired Adding a generator to an existing unit requires the installer to be sure that generator wiring...

Страница 17: ...s require no adjustments Receiver modules are factory set to the range specified on the order and alarm setpoints will be set to default values unless otherwise specified on the order Sensor transmitt...

Страница 18: ...TROUBLE alarm is activated 3 Isolated 4 20 mA output signal proportional to gas concentration 4 Isolated remote reset input terminals for remote alarm acknowledgment 5 Power for operation of an A11 s...

Страница 19: ...TROUBLE NC trouble normally closed contact 11 TR Transmitter Input 11 TROUBLE C Trouble common 12 TR Transmitter Input 12 TROUBLE NO Trouble normally open contact NOTE Relay contact designation is sho...

Страница 20: ...l latching operation Relay 3 Configured to trip at the Alarm setpoint and set for normal latching operation Alarm Delay Configured for 2 second delay Warning and Alarm setpoints are factory set to sta...

Страница 21: ...GasSens Gas Detection System Section 2 A14 Receiver Module O M Manual A14 RK 8 06 2 4 Figure 2 4 Configuration Switch Functions 0110PM...

Страница 22: ...01 37 0100101 69 1000101 6 0000110 38 0100110 70 1000110 7 0000111 39 0100111 71 1000111 8 0001000 40 0101000 72 1001000 9 0001001 41 0101001 73 1001001 10 0001010 42 0101010 74 1001010 11 0001011 43...

Страница 23: ...et to actuate when the gas concentration either goes above or falls below the setpoint Most gas leak detection applications require alarms to activate above a specific setpoint but alarms for oxygen d...

Страница 24: ...y may be selected if required in a specific application The delay time of either 2 or 10 seconds affects both the warning and alarm indicator lamps and the associated relays External Horn Relay Relay...

Страница 25: ...lly the display will spike when power first comes on and will slowly recover to zero over the 5 minute period in which alarms are inhibited NOTE Sensors may require up to 12 hours to stabilize after p...

Страница 26: ...manpower normally required for routine testing Auto Test is an electrochemical gas generator fixed to the gas sensor and controlled from the receiver Every 24 hours the receiver automatically activate...

Страница 27: ...test press and hold the A R button for 2 seconds and all front panel indicators will light The horn will also sound briefly Immediately release the button and the indicators will return to normal Dur...

Страница 28: ...e unsuccessful the TROUBLE lamp will light and the alarm relay and horn will activate Pressing the A R button will silence the horn but the alarm cannot be reset for at least 10 minutes after a failur...

Страница 29: ...to a failure of the generator If proper sensor operation has been verified the automatic daily activation of the test function can be bypassed until a replacement generator has been installed To deac...

Страница 30: ...correctly but does not respond when test gas is applied to sensor transmitter 1 Disconnect transmitter connections at terminals 11 and 12 of TB1 Check the voltage on the terminals with a voltmeter Th...

Страница 31: ...ONT PANEL 34 0009 PLUG ON TERMINAL BLOCK 38 0006 TOP HALF OF ENCLOSURE 80 0002 PC BOARD ASSEMLBY BOTTOM HALF OF ENCLOSURE 80 0002 Part Number Description 00 0056 Complete receiver module Specify Gas 8...

Страница 32: ...draw approximately 400 mA when activated The power supply is internally fused at 2 Amps The fuse is not user replaceable Note Only Qualified Service Personnel will replace the fuse using the same typ...

Страница 33: ...eceiver Module 1 12 Receiver Module 2 C External Battery 2 C Receiver Module Common 2 C Receiver Module Common 3 Earth Ground 3 Earth Ground 3 Earth Ground TB4 TB5 1 L AC power hot 85 255 VAC 1 NC Pow...

Страница 34: ...4 RK 8 06 3 3 POWER SUPPLY PARTS LIST Part Number Description 00 0055 Complete power supply module 81 0064 Module enclosure top and bottom 34 0011 Front overlay 38 0065 AC power terminal block plug 3...

Страница 35: ...ery back up unit and the mounting hole centers Two conduit hubs are supplied with the unit one for use on the battery back up enclosure and one for use on the receiver enclosure When mounting the batt...

Страница 36: ...the charging current to the battery to a maximum of 0 75 amps This prevents possible damage to the battery due to an excessively high charge current Second it isolates the battery from the detection...

Страница 37: ...circuit board 80 0009 NEMA 4X enclosure top and bottom 48 0010 Battery bracket 29 0002 Battery 12 V 4 A H 92 0022 Self tapping screws Pkg Of 2 44 0017 Pg 16 to 1 2 NPT conduit hub 44 0018 Pg 16 Seal R...

Страница 38: ...ires to the interconnect wiring running to the alarm unit This wiring should be kept separate from AC power wiring to avoid accidental connection of AC power to the strobe which will damage the lamp T...

Страница 39: ...e mounted using screws or bolts as required Figure 5 1 provides the dimensions for both the standard and explosion proof transmitters Standard enclosures will accommodate 6 or 8 screws which are not s...

Страница 40: ...15 5 2 Notes 1 Enclosure Ratings Nema 4X IP 66 2 Enclosure Material Polystyrene standard gray 3 Knockouts Pg 11 75 dia Pg 16 90 dia 4 These are the dimensions between knockouts and are typical for 3...

Страница 41: ...GasSens Gas Detection System Section 5 A11 10 Br2 Sensor Transmitter O M Manual Revision E 10 15 5 3 Figure 5 2 Explosion Proof Sensor Transmitter Dimensions ATI 046 ATI 0170...

Страница 42: ...nsmitter uses an electrochemical sensor manufactured by ATI It is designed to measure Br2 gas concentration in air with a maximum of sensitivity and a minimum of interference from other gases Unfortun...

Страница 43: ...linder chlorine standards are available but should be used with caution Low concentrations of chlorine have not proven to be stable in a cylinder over extended periods of time NOTE If alarm relays at...

Страница 44: ...he DVM reading for the next 5 minutes If bromine or some interfering gas is present in the ambient air the value on the DVM will begin to decline If the value remains stable 0 02 the sensor is at zero...

Страница 45: ...ENSOR RESPONSE TEST While zero and span adjustments are required only periodically gas sensors should be checked regularly for proper response For systems not equipped with Auto Test manual sensor res...

Страница 46: ...sensor to completely stabilize Then perform a zero and span as described on pages 4 and 5 GENERATOR REPLACEMENT Auto Test gas generators are warranted for 12 months and will generally last for 24 mon...

Страница 47: ...sensor transmitter assembly including sensor 00 0002 Bromine gas sensor 00 0097 Chlorine gas generator with gland seal used to Auto Test Br2 systems 01 0018 Transmitter circuit board 80 0012 NEMA 4X e...

Страница 48: ...improper storage or extended exposure to excessive gas concentrations Should inspection indicate that sensors have failed due to any of the above the warranty shall not apply The Manufacturer assumes...

Страница 49: ...DUCTS NH3 Ammonia CO Carbon Monoxide H2 Hydrogen NO Nitric Oxide O2 Oxygen CO Cl2 Phosgene Br2 Bromine Cl2 Chlorine ClO2 Chlorine Dioxide F2 Fluorine I2 Iodine HX Acid Gases C2H4O Ethylene Oxide C2H6O...

Отзывы: