SECTION 2 INSTALLATION INSTRUCTIONS

2.1

Unpacking

Unpack the instrument and inspect for shipping damage. Report any

damage to the carrier immediitely.

2.2

Locating

Select a location for the controller where it will not be subject to excessive

shock vibration, dirt moisture or oil. The ambient temperature of the area
should be between  3 2 º  and 131  º F  (A model  DC-15 dust, oil and water resis-

tant cover is available to protect from harsh environments.)

2.3

Mounting

Mount the controller into a 92 mm (3  5/8”) square cutout See figure for the

cutout and case dimensions. The plug-in controller does not have to be
removed from its housing for mounting. Remove two screws that hold the
mounting slides and then remove the slides. Insert case from front panel

and  re-install the two slides and two screws. Do not over-tighten screws. The

length of the slides must be reduced if the controller is to be mounted in an

extra thick  panel. If the controller has been unplugged from its housing, the
top of the housing can be determined because it features the serial tag.

2.4

Removing Unit

The 6075 can be removed from its housing by pulling firmly on the black
front bezel. If a communication port is connected, it should be removed
first

Содержание 6075 series

Страница 1: ...SERIES 6075 TEMPERATURE CONTROLLERS WITH AUTO TUNING PID AND PLUG IN COMPUTER INTERFACE...

Страница 2: ...PAID BY THE PUR CHASER AND UNDER NO CIRCUMSTANCES SHALL BE LIABLE FOR SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES THE PRICE STATED FOR THE EQUIPMENT IS A CONSIDERATION IN LIMITING SELLER S LI...

Страница 3: ...g 5 2 3 Mounting 5 2 4 Removing Unit 5 2 5 Case Dimensions 6 SECTION 3 OUTPUT MODULES 7 3 1ModuleDescription 7 SECTION 4 BASIC WIRING 8 4 1 Typical Wiring Examples 8 4 2 Wiring Thermocouple and RTD Ci...

Страница 4: ...ify and Store 32 SECTION 7 CALIBRATION 33 7 1 Zero and Span Adjustments 33 Factory Set SECTION 8 TROUBLESHOOTING 34 8 1 Troubleshooting General 34 8 2 Troubleshooting Communications 35 FIGURES 1 1 Ord...

Страница 5: ...essure safety control Even the best components can be damaged or may not failsafe WarningNotes 1 B Output for resistance load only 2 An open thermocouple will disable the INDEX function 3 Note also th...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...mm 3 5 8 squarecutoutSeefigureforthe cutout and case dimensions The plug in controller does not have to be removed from its housing for mounting Remove two screws that hold the mounting slides and the...

Страница 10: ......

Страница 11: ...ll output to loads having an input impedance of 500 Ohms or less The cycle time setting must be ZERO for smooth current output Module Type S Similar to F but pulsed 20 Vdc output for driving solid sta...

Страница 12: ......

Страница 13: ......

Страница 14: ...T AS POWER LINES If shielded RTD wire is used terminate the shield only at the controller end using the comer screw provided for that purpose NOTE RTDs tend to be shock sensitive and require extra car...

Страница 15: ...l etc Other recommended practices include Run sensor wires separately shield if possible and ground only one end oftheshield Install 01 ufd 100V or greater capacitors from each sensor terminal to case...

Страница 16: ...2Stepscan rate Slow and Faster after 5 seconds Index Key Selects Parameters to be addressed STAND BY CANCEL Key Disables outputs Unit is put in idle mode LED above switch lights in STAND BY mode STAN...

Страница 17: ......

Страница 18: ...is range A rear position is range B grouped s offered A 01F No Jumper 26F A 33F A 22F No Jumper 22C B 02F B 32F B 26C Consult Serial Tag for actual range and sensor type ordered Ranges are defined in...

Страница 19: ...y labelled SET POINT which allows the user to EXIT parameters 2 thru 16 back to parameter 1 set point After changing a value the ENTERKeymustbepressed Thisentersthenewvalueinmemory Ifit is not pressed...

Страница 20: ...s will be off On completion of inital setup push the key again LED off for normal operation press the INDEX key until parameter 9 cd appears in the process displayarea a Set 14 in lower display to gai...

Страница 21: ......

Страница 22: ...d using the INDEX key Select the level of security desired and enter the appropriate value into memory 1 Allows changes to set point only 8 Allows changes to first nine parameters only 14 Allows chang...

Страница 23: ...settings can be altered When neither 1 8 or 14 are entered only the access code can be altered NOTE4 Theconfigurationcodeallowstheusertoconfigurethealarmsfor process deviation high or low energizing T...

Страница 24: ...ate tuning Less than 100 F may not yield effective tuning settings Multi zone applications require Auto Tune units on each zone and simultaneous warmup Loss of power or a turn off during the Auto Tune...

Страница 25: ...type of cooling used 00 Oil cooling Use this Setting if No cooling is used 01 Air cooling Forced air 02 Water cooling above 212 F set point Operating Instructions Read Damping Settings before proceed...

Страница 26: ...parameters Also refer to Ziegler Nichols Tuning Method It is possible to set or fine tune the three mode parameters manually To manually enter parameters 1 Press Index button until Rt Rate HG Heat Gai...

Страница 27: ......

Страница 28: ...instability and temperature overshoots on startup Remember that the reset automatically tracks the rate rt adjustment 7 Connect cooling apparatus Observe control stability 8 If oscillation occurs lowe...

Страница 29: ......

Страница 30: ...erface box This module allows bi directional data transfer over a shielded twisted pair The twisted pair is a transmission line with drops to communicating devices Since it is a transmission line term...

Страница 31: ...should be connected to frame ground at one end only Signal ground is connected at both ends The RS232 module is configured for active operation 6 1 3 20 mA Current Loop This module allows bi direction...

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ...ie index key on the 6075 press the up down keys on the 6075 until both instruments agree press the ENTER key Set in a value on the calibrator equivalent to the high end capability of the unit under te...

Страница 38: ...k of case Repair or replace thermocouple Check for reversed thermocouple Wrong thermocouple type connected or internal range jumper in wrong position Check serial tag for sensor type and then check pr...

Страница 39: ...ATHENL Athena Controls Inc 5145 Campus Drive Plymouth Meeting PA 19462 Tel 610 828 2490 Fax 610 828 7084...

Отзывы: