CALIBRATION
MENU
How Do I Get Here?
1. Press for
3 seconds until
menus appear.
ONLY AVAILABLE
UNDER FACTORY
SECURITY LEVEL.
2. Press until
appears.
3. Press until
appears.
The SV display will
alternate between
the parameter and
its value.
4. Press or
to make selection
Display
Parameter
Available Selections
Toggles with the temperature value that should be input to
perform the low calibration operation. The low calibration
operation is triggered by pressing the up arrow
key.
Toggles with the temperature value that should be input to
perform the high calibration operation. The high calibration
operation is triggered by pressing the up arrow
key.
Please note that this menu can only be seen / used when the controller has been set to the
highest security setting - Factory (
) . We strongly recommend that under normal operations,
this menu is deactivated.
The calibration menu does not contain confi guration parameters, instead it is used to display the values for
which a simulated input should be applied to the controller input terminals during calibration of the zero off set
and the span adjustment. It is also used to initiate the calibration operation after the controller has been
prepared.
You do not have to calibrate every new controller. When your controller was ordered, you specifi ed an input
type for which the unit was calibrated at the factory for the type of input specifi ed.