We recommend initial set up starts at the Input menu where the first parameter that needs to be set is Input
Type.
The remaining Input Menu parameters will change, depending upon whether a linear input type or a
temperature input type is selected. Other menu parameters related to the sensor range may also change.
INPUT MENU
Input Jumper Settings
Display
Parameter
Available Selections
Input Type
-
Type J thermocouple
- Type B thermocouple
- Type C thermocouple
- Type E thermocouple
- Type K thermocouple
- Type N thermocouple
- Type NNM thermocouple
- Type R thermocouple
- Type S thermocouple
- Type T thermocouple
- Platinel II thermocouple
- 100 ohm platinum RTD
- digital RTD
- 0 - 20 mA
- 4 - 20 mA
- 0 - 10mV
- 0 - 50 mV
- 0 - 100 mV
- 10 - 50 mV
- 0 - 1 V
- 0 - 5 V
- 0 - 10 V
- 1 - 5 V
Input Type
JMPØ1 JMPØ2
Thermocouple Out Out
RTD
Out Out
Voltage <100 mV
Out
Out
Voltage >100 mV
In
Out
Current Process
In
In
Note: When you ordered your controller, an input type was specified and the controller was set up
accordingly and calibrated for that input type at the factory. If you decide to change input type from
thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the
“Calibrate All” option. If you are changing from a temperature input type to a linear input type, you MUST
recalibrate and change the jumper settings as indicated in the above table.
How Do I Get Here?
1. Press for 3
seconds until menus
appear.
2. Press until
appears.
3. Press until
appears.
The SV display will
alternate between
the parameter and
its value.
4. Press or
to make selection
PARAMETER OPTIONS WITHIN INDIVIDUAL MENUS