CONTROL METHODS
HeatNet Control V3 3.x
Page 55
DHW Method 5a: Local DHW Tank Heating using a 10k Tank Sensor.
Figure 40
Example:
DHW Heating to a Local Boiler’s Tank,– Method 5a
MASTER
MEMBER
2
MEMBER
3
HNET
Lo
ca
l P
u
m
p
Lo
ca
l P
u
m
p
HNET
DH
W
P
u
m
p
DH
W
P
u
m
p
Sy
st
em
R
et
u
rn
Sen
so
r
Domestic Hot
Water
Domestic Hot
Water
Tank Sensor
Su
p
p
ly
H
ea
d
er
S
e
n
so
r
Lo
ca
l P
u
m
p
System Pump
Sy
st
em
Re
tu
rn
S
e
n
so
r
E
xp
a
n
sio
n
T
an
k
Cold Water
Makeup
HeatNet
HeatNet
Supply
Make Up
Supply
Make Up
WM
Tank Sensor
DH
W
S
en
so
r
DH
W
S
en
so
r
HeatNet
Sy
st
em
P
u
m
p
System
Supply
System
Return
DHW METHOD 5a: Local DHW Tank Heating Override using a 10K Type II Tank Sensor.
In DHW METHOD 5a: Local DHW Tank Heating Override, the MASTER’s
Heat Demand
input enables space heating by
energizing the system pump and maintaining the Heating Setpoint at the MASTER’s System Header Sensor using the available
MEMBERs. A MEMBER boiler will enable its local pump when called to service a heating call by the MASTER. Each
MEMBER has its
OR OVR
input jumped to enable local DHW heating using its DHW Sensor. When a DHW tank sensor calls
for heat, the local boiler goes offline from the MASTER. The boiler can disable its local pump (Programmable) and enables its
DHW pump/valve to service the local tank until the tank sensor has been satisfied. Once the call for DHW heat has been satisfied,
the boiler is placed back online for the MASTER to service the main heating loop.