1.2

The principle of operation

The gas detectors measures the concentration of a given component, and then turns it – depending on the

variety (described below) – to understandable signal for other devices of the gas safety system. In addition
to the implementation of the measurement, the detector analyses the value of the measured concentration

and may provide information about exceeding the following threshold values:

warning 1,
warning 2,
alarm,
gas overload (threatening with the sensor damage).

In   addition   to   the   above,   the   gas   detector   is   a   self-diagnostic   device   –   in   the   case   of   detection   of
malfunctions, it informs the user about it.

1.3

Gas detector status

Mode

Description

Correct
operation

The detector operates properly and makes measurements. The concentration value of the gas
being measured does not exceed threshold values and no irregularities in the device operation
were detected.

Warning 1

Signalled after exceeding the gas concentration above the specific value.

Warning 2

Signalled after exceeding the gas concentration above the specific value.

Alarm

Signalled after exceeding the gas concentration above the alarm threshold.

Gas overload

Gas concentration has exceeded the overload threshold value. If such is the case, the sensor may
be damaged or its sensitivity and shelf-life may be reduced.

Lock

1

Gas concentration is above the overload value (the default value is 100% LEL). The detector is
locked (see appendix [3]) – the last value of the concentration is shut. The detector does not make
measurements. It is possible to unlock the condition by means of sending the applicable command
from the control unit or from the superior system.

Removing the lock on a detector which is in the conditions of concentration
above the measuring range can damage the sensor.

Warm up

After turning on the detector's power supply, the sensors's working parameters stabilize for some
time.

Measurements   are   also   taken   during   preheating   of   the   detector   but   no
information   about   gas   hazards   is   provided.   Be   aware   that   exceeding   of   gas
concentration above its maximum measurable range may led to damage of the
gas sensor. 

Calibration

In this state the detector allows to change your settings. In the calibration mode it is also possible
to examine the detector without raising an alarm (in fact, the behaviour of the system will be
determined by the interpretation of the data by the central system). The detector can be switched
to this state using the appropriate software tools.

1

The condition is present only for the detectors with a catalytic sensor. Active lock mechanism.

s. 6|27

User Manual: POD-064-ENG R05

Содержание ProGas 4

Страница 1: ...POD 064 ENG R05 User Manual Gas Detector ProGas 4 Product code PW 017 PG4 X...

Страница 2: ...ring Detection and Reduction of gas hazards We invite you to familiarize yourself with our offer on www atestgaz pl Atest Gaz A M Pachole sp j ul Spokojna 3 44 109 Gliwice Poland tel 48 32 238 87 94 f...

Страница 3: ...nts during the entire lifetime of the product Use of unauthorized spare parts different from the ones listed in Table 13 is strictly forbidden How to use this manual The following symbols of optical i...

Страница 4: ...stant output signals 13 Table 6 Intervals of the output current according to the detector status 13 Table 7 Operation modes of gas detectors with the Bluetooth interface 14 Table 8 Configuration of th...

Страница 5: ...ring head to achieve the topmost metering parameters Upon request optional upgrade to IP66 IP67 protection class provided that a suitable membrane is applied Customized configuration of the electric c...

Страница 6: ...rload threshold value If such is the case the sensor may be damaged or its sensitivity and shelf life may be reduced Lock1 Gas concentration is above the overload value the default value is 100 LEL Th...

Страница 7: ...systems e g with industrial controllers details in section 4 3 Relays it allows the direct use of gas detectors to control executive devices details in section 4 4 1 6 Gas detector with an FL C head G...

Страница 8: ...a gas of unknown composition or excessive concentration is forbidden since it may lead to irreversible damage of the gas sensor All activities related to connecting detectors signallers and other sys...

Страница 9: ...ion with its measuring head looking down see Figure 3 Other mounting positions may compromise IP class of the device When screwing the cover of the detector enclosure pay attention to the thread of th...

Страница 10: ...xygen content in the environment especially in the case of catalytic detector pellistor type oxygen content less than 18 significantly reduces the sensitivity of the detector the presence of other gas...

Страница 11: ...ssible options of the terminal block layouts are shown on illustrations below 4 1 1 RS 485 digital communication port Figure 5 Electric connections for the option with the RS 485 port Port designation...

Страница 12: ...he RS 485 port transmit output signals in the digital form see Appendix 4 Each detector provides information about its status by transmission of the following parameters result for measurements of gas...

Страница 13: ...lure 4 mA No alarm 9 mA Warning 1 11 mA Warning 2 13 mA Alarm 22 mA Detector overloaded Table 6 Intervals of the output current according to the detector status The specific operation mode with respec...

Страница 14: ...of gas detectors with the Bluetooth interface The picture below depicts how to mount the permanent magnet on the detector housing only strong neodymium magnets are suitable Be careful to mount the per...

Страница 15: ...f outflow leakage gush volatility of gas in the case of substances of low volatility the detector should be located as close as possible to the expected leak the impact of environmental conditions see...

Страница 16: ...hen performing electrical connections it is necessary to observe the following order make sure that the connected cables are disconnected from any electrical circuits and potentials make sure that dur...

Страница 17: ...ables preferably in separate trays The electric circuits of the Gas Safety System is not intrinsically safe Damage of any cable can lead to a danger If the connection was made with the use of multi wi...

Страница 18: ...it is recommended to carry out commissioning of the entire system in several steps with successive connection and commissioning of subsequent detectors It makes easy to reveal and remedy any possible...

Страница 19: ...adjustment calibrations replacement of fast wearing parts periodical inspections 5 6 1 Resetting Gas sensors are characterized by a certain drift of zero over time It s mean that during operation the...

Страница 20: ...to the control unit a common data bus transfers data between detectors and the control unit directly to the detector when you open the cover or an Android device directly to the detector for devices...

Страница 21: ...en contamination of the piece of sintered material is found out loosen the locking screws in the bushing with a 1 5 mm Allen wrench see Figure 3 replace the housing with the attention paid to make sur...

Страница 22: ...wrench see Figure 3 unscrew the sensor housing do not allow bushing to rotate due to the possibility of damage to the connector inside the enclosure remove the filling stuff unscrew the bolts in the c...

Страница 23: ...symbol on a product or on its packaging indicates that the product must not be disposed of with other household waste Instead it is the user s responsibility to ensure disposal of waste equipment by h...

Страница 24: ...x Floating contacts 24 V 0 3 A Not protected against overloading Digital communication parameters RS 485 Teta RS 485 Modbus ASCII RTU Sigma Bus 19200 Bd 7E1 Teta Bus Protection class III Dimension Se...

Страница 25: ...material size 2 5 mm Depends on ambient conditions Atest Gaz PWS 055 A 3 HW Housing Atest Gaz PWS 060 B 4 Membrane with sealings Depends on ambient conditions Atest Gaz 5 Sensor with gasket Depends on...

Страница 26: ...ter fast reduced T90 and membrane made of stainless steel FH With sinter fast reduced T90 made of stainless steel warmed FH M With sinter fast reduced T90 and membrane made of stainless steel warmed H...

Страница 27: ...ce and failure codes of Gas Detectors of PW 017 PW 044 and PW 093 type 6 PU Z 074 ENG Example of connection cables for gas detector PW 017 and PW 044 with 4 20 mA output 7 PU Z 076 ENG Example of conn...

Страница 28: ...n hazardous substances in electrical and electronic equipment EN 50581 2012 other EN 60529 1991 This declaration of conformity is issued under the sole responsibility of the manufacturer Purpose and s...

Страница 29: ...as detectors produced by Atest Gaz 2 ProGas 4 Gas Detector PW 017 PG4 Converter module PELm Catalytic 40 LEL Display 0 Without Measuring head HL With sinter made of stainless steel Enclosure AL Alumin...

Страница 30: ...gas concentration in the place of the detector operation is beyond the measuring range of the sensor a permanent sensor damage or a false reading of the concentration can occur as a result of the non...

Страница 31: ...The meaning of the bits is described in the table below Bit Name Description 0 Collective_W1 Gas concentration is above first warning threshold 1 Collective_W2 Crossing the second warning threshold 2...

Страница 32: ...ing with green The first warning threshold is exceeded red Alarm Modulated sound signal yellow Detector s critical failure white Test calibration 3 Gas detector with LCD display D LCD 3 1 Description...

Страница 33: ...Overload The gas concentration exceeds the overload value Indicators 1 2 and ALARM and in the panel are continuously lit The detector still performs measurement which is indicated by continuously lit...

Страница 34: ...sible indicator two flashes per 2s _ _ _____ The display shows TEST message Non critical failure Detector malfunction that may negatively impact its measurement accuracy e g exceeding of time until pe...

Страница 35: ...tact atestgaz pl p 4 5 Appendix PU Z 073 ENG R04 ALARM 2 1 Warning 2 Gas concentration Warning 1 ALARM Overload ALARM 2 1 Sensor Sn0 2 PID electrochemical IR Catalytic sensor No danger Description No...

Страница 36: ...ment path damage of the measurement path sensor signal is too high sensor signal is too low damage of the temperature detector damage of the program block damage of the data block AWN failure code Non...

Страница 37: ...ate external diameter mm Maximum cable length m Outdoor installations Indoor installations LiYCYv 300 500 V 3x1 0 LiYCY 300 500 V 3x1 0 9 1 155 LiYCYv Nr 300 500 V 3x1 0 LiYCY Nr 300 500 V 3x1 0 9 1 1...

Страница 38: ...75 LiYCY Nr 300 500 V 6x0 75 11 3 75 LiYCYv 300 500 V 6x0 75 LiYCY 300 500 V 6x0 75 11 3 75 LiYCYv Nr 300 500 V 8x0 5 LiYCY Nr 300 500 V 8x0 5 11 9 100 LiYCYv 300 500 V 8x0 5 LiYCY 300 500 V 8x0 5 11...

Страница 39: ...with a more accurate round cross section made with the use of pressure better sealing in the Ex glands 3 Power source The power supply line should be designed in such a way that at the lowest expecte...

Страница 40: ...V min UPS supply voltage 21V min permissible sensor supply voltage 12 V distance between the control unit and the sensor 800 m Calculations max current consumption of the sensor 2 W 12 V 0 167 A permi...

Страница 41: ...f the cables isolated clamp sleeve shall be placed he conductive part of the clamp sleeve shall have applicable length see 1 For the systems with RS 485 interface it is necessary to make sure that A a...

Страница 42: ...d that cables should be ordered connecting cables should be kept as far away from the detector electronics as possible and routed as directly as possible to the crimp connection it is necessary to min...

Страница 43: ...rocess e g weather conditions safety potential hazard generated by the mixture criterion B These both criteria have an impact on the final cost of the calibration services and level of competence requ...

Страница 44: ...of flammable components 60 LEL concentration of toxic components NDSCh2 oxygen concentration 25 vol tank 3 dm3 water capacity and p 70 atm specified liquid chemical compounds e g glycerol 1 2 propaned...

Страница 45: ...www atestgaz pl Notes...

Страница 46: ...www atestgaz pl Notes...

Страница 47: ......

Страница 48: ...M Pachole sp j Spokojna 3 44 109 Gliwice tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl For more details on our devices and other products and services offered by us visit www ate...

Отзывы: