4.1.2
Teta Bus digital communication port
Figure 6: Electric connections for the option with the Teta Bus port
Port designation
Name
Pin
Description
X1
TETA BUS
-, +
Combined transmission and power supply lines
4-20
S
4 – 20 mA current output
X2
R1.1 – R3.2
Relays terminals
Table 4: Connections diagram for the option with Teta Bus port
4.2
RS-485
Communication via the RS-485 employs either the Modbus ASCII or the Sigma Bus protocol (when the
detector communicates with other devices of the Sigma system).
Detectors provided with the RS-485 port transmit output signals in the digital form (see Appendix [4]). Each
detector provides information about its status by transmission of the following parameters:
result for measurements of gas concentration expressed as percentage ratio of the full range,
information whether warning /alarms thresholds are exceeded or not,
status details, e.g. possible failures or defect, etc.
4.3
Current output
4.3.1
Operating modes – direction of current flow
The current output can be used in two modes: sink or source. The diagram below explains how to connect
the detector for each of the operating mode.
Figure 7: Connection of a gas detector according to the direction of current flow
s. 12|27
User Manual: POD-064-ENG R05
-
+
S
A
Source
-
+
S
A
Sink
R
OBC
U
S
Содержание ProGas 4