General information

The Control Unit Module  MOD CNV PK420 enables extension of an existing Gas Safety System and is
meant to convert an On/Off signals received from relay outputs of the Control Unit into a discrete signal

4..20 mA, whereas an active signal with the highest priority is transferred to the output of the module (See
Table 2).
The unit produces a discrete output signal as an electric current within the range from 4 to 20 mA that

enables wiring a Control Unit Module with a relay output to a Control System or a Control Unit that has an
analog input 4..20 mA. Such a solution enables: 

monitoring of a transmission line, where failures (shorts, line breaks) are distinguished from

regular operation and an emergency alarm (see Figure  4),
transmission of an input signal for further processing by a Central Control Unit (e.g. EcoAlpa, Alpa
P17, MOD LED8, etc.). 

For normal operation of the unit the PK FAILURE output of a control device wired to the MOD CNV PK420

module must be inverted to match the logic levels adopted for the solution (see Table 2 and Figures 1 and
4) when relevant inputs of the signal converter are closed, the module produces an output signal with the

appropriate current amperage:

Status of contacts at the

inputs to the MOD CNV

PK420 module 

Output current of the

converter module 

Meaning for Control Unit of

the Alpa series

Order of priorities 

‘+’ closed to ‘AL’

15 mA

ALARM

1 (highest)

‘+’ closed to ‘OS’

10 mA

WARNING 

2

All contact open 

2.5 mA

FAILURE

3

‘+’ closed to ‘P’

5 mA

OPERATION 

4 (lowest)

Table 2: Specification of output signals produced by the Signal Converter Module MOD CNV PK420

Figure 1:  Switching of contact for an inverted FAILURE relay output of the control unit driving the signal

converter

s. 5|9

User Manual: POD-016-ENG R01

COM

NO

NC

NO FAILURE

COM

NO

NC

FAILURE

Содержание MOD CNV PK420

Страница 1: ...POD 016 ENG R01 User Manual Control Unit Module MOD CNV PK420 Product code PW 048 A...

Страница 2: ...ring Detection and Reduction of gas hazards We invite you to familiarize yourself with our offer on www atestgaz pl Atest Gaz A M Pachole sp j ul Spokojna 3 44 109 Gliwice Poland tel 48 32 238 87 94 f...

Страница 3: ...guarded may need consideration of other requirements during the entire lifetime of the product How to use this manual The following symbols of optical indicators status are used throughout the documen...

Страница 4: ...ication of output signals produced by the Signal Converter Module MOD CNV PK420 5 Table 3 Specification of the terminal block 6 Table 4 Maximum runs of cable sections 7 Table 5 Technical specification...

Страница 5: ...her processing by a Central Control Unit e g EcoAlpa Alpa P17 MOD LED8 etc For normal operation of the unit the PK FAILURE output of a control device wired to the MOD CNV PK420 module must be inverted...

Страница 6: ...rs in Section 5 AL Tripping line for the ALARM signal OS Tripping line for the WARNING signal P Tripping line for the OPERATION signal Plus pole for tripping signals 2 Output Output port Plus pole for...

Страница 7: ...imilar cables with sufficient cross section of cores see Table 5 Maximum runs for the cable sections to wire the PK420 converter to a Control Unit with consideration of cable core cross section a list...

Страница 8: ...f with other household waste Instead it is the user s responsibility to ensure disposal of waste equipment by handing it over to a designated collection point for the recycling of waste electrical and...

Страница 9: ...ut the state with the higher priority is transferred Protection class III Dimension See Figure 2 Acceptable cables 1 1 5 mm2 Enclosure Self extinguishing PPO Weight 0 1 kg Mandatory periodic inspectio...

Страница 10: ...he use of certain hazardous substances in electrical and electronic equipment EN 50581 2012 This declaration of conformity is issued under the sole responsibility of the manufacturer Purpose and scope...

Страница 11: ...Gliwice Poland VAT No PL 9691433231 tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl Appendix PU Z 077 ENG R01 s 1 1 Alpa MOD LED8 MOD CNV PK420 Channel 1 EcoAlpa Alpa P17 S Detector...

Страница 12: ...chole sp j ul Spokojna 3 44 109 Gliwice Poland VAT No PL 9691433231 tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl Appendix PU Z 109 ENG R01 s 1 1 Input Channel 1 EcoAlpa Alpa P17...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Отзывы: