Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and
Password information has become corrupted, or you have forgotten it, for
example), you can clear the login information with the following procedure:
1. Disconnect all devices and peripherals connected or plugged into the PDU.
2. Power off the eco PDU and remove its housing.
3. Short the jumper labeled J3 (PIN1 and PIN2).
4. Power on the eco PDU.
5. After the beep indicates its been successfully powered on, power off the
PDU.
6. Remove the jumper cap from J3.
7. Close the housing and start the eco PDU.
After you start, you can use the default Username and Password to log in.