UPS User Manual
40
Acceptable Input Voltage Range
Setting
Display: 19
Display: HS
Parameter 2: Acceptable high voltage
point and acceptable low voltage point
for
input voltage range. Press the Up or Down
key to adjust the values.
HLS:
Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300:
setting the high voltage point
in parameter 2. (Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/150:
setting the high voltage point
in parameter 2. (Default: 150Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
110/120/130/140/150/160:
setting the low
voltage point in parameter 2. (Default:
110Vac)
For 100/110/115/120/127 VAC models:
55/60/65/70/75/80:
setting the low voltage
point in parameter 2. (Default: 55Vac)
Exit
Display: 00
Exit UPS Setting.
Parameter 1 & Interface Display
Parameter 2 Description
Содержание NRGence HV Series
Страница 10: ...UPS User Manual x This Page Intentionally Left Blank...
Страница 16: ...UPS User Manual 6 UPS HV Series Rear View...
Страница 22: ...UPS User Manual 12...
Страница 24: ...UPS User Manual 14 4 Replace the front panel back to the unit...
Страница 29: ...Chapter 2 Hardware Setup 19 3 Replace the front panel back to the unit...
Страница 34: ...UPS User Manual 24 6 On the front side of the unit reconnect the battery connector and reattach the front cover...
Страница 36: ...UPS User Manual 26 This Page Intentionally Left Blank...
Страница 58: ...UPS User Manual 48 This Page Intentionally Left Blank...