ATECPOOL SIROCCO HEAT PUMP > Common Failure Solution
15
Code
Parameters
Fault Description
Fault Solution
1
IPM over current
IPM module issues
Replace the inverter module
2
Abnormal press
synchronization
Compressor failure
Replace the compressor
4
Reservation
--
--
8
Compressor output phase loss
Compressor connection broken, bad contact
Check compressor circuit
16
DC bus voltage is low
Input voltage is too low, pfc module fault
Check input voltage, replace
module
32
DC bus voltage is high
Input voltage is too high, pfc module fault
Replace the inverter module
64
Imp temp. is too high
Fan failure, air duct blockage
Check fan and air duct
128
Imp temp. fault
Short circuit or open circuit fault of IPM sensor Replace the inverter module
257
Communication failure
The inverter module has not received the
command from the main controller
Check the communication
line between main controller
and inverter module
258
AC input phase loss
Input phase loss (available for three-phase
module)
Check the input circuit
260
AC input over current
Input three-phase unbalance (available for
three-phase module)
Check the three-phase
voltage
264
AC input voltage is low
Input voltage is low
Check the input voltage
272
High pressure failure
Compressor high voltage failure (reservation)
288
IPM temp. too high
Fan failure, air duct blockage
Check fan and air duct
320
The peak current of the
compressor is too high
Compressor current is too large, the driver and
the compressor do not match
Replace the inverter module
384
PFC module temp. is too high
PFC module temp. is too high
Check the PFC module
272
High pressure failure
Compressor high voltage failure
(Reservation)
288
IPM temp. is too high
Fan failure, air duct blockage
Check fan and air duct
320
The peak current of the
compressor is too high
Compressor current is too high, the
driver and the compressor do not
match
Replace the inverter
module
384
PFC module temp. is too
high
PFC module temp. Is too high
Check the PFC module