4. Electrical Connection
Power Supply Wires Size
Model
Power Supply Wires
Electricity Supply
Cable Diameter
Specification
AIHP115
220-240V/50Hz
3×2.5mm²
AWG 14
AIHP180
220-240V/50Hz
3×2.5mm²
AWG 14
AIHP212
380-415V/3N~/50Hz
5×4.0mm²
AWG 12
AIHP253
380-415V/3N~/50Hz
5×4.0mm²
AWG 12
WARNING: Power supply of heat pump must be disconnected before any operation.
➢
Please comply with the following instruction to connect the heat pump.
➢
Step 1: Detach electrical side panel by a screwdriver to access the electrical
terminal block.
➢
Step 2: Insert cable into heat pump unit port.
➢
Step 3: Connect power supply cable to terminal block according to the diagram below.
4.1 Wiring:
a. Connect to appropriate power supply; the voltage should comply with the rated
voltage of the products.
b. Earth the machine well.
c. Wiring must be handled by a professional technician according to the circuit diagram.
d. Set leakage protector according to the local code for wiring (leakage operating current ≤ 30mA).
e. The layout of power cable and signal cable should be orderly and not affecting each other.
⚠