Operating conditions: 
  Operating temperature range: -30 to +80 °C, over +70°C switch LCD display OFF 
  Operating humidity range: 0 to 100 %RH 

    

Outer characteristics in accordance with EN 33-2000-3: 

normal environment with the specifications: AE1, AN1, BE1 

Working position: the stem downwards 

Electromagnetic compatibility: complies EN 61326-1  

 

Not allowed manipulations: 
It is not allowed to operate the device under other than specified conditions in technical 

parameters. Devices are not designed for locations in chemically aggressive environment.  

Storing conditions: temperature -30 to +80 °C, humidity 0 to 100 %RH without 

condensation 

Dimensions: 89 x 73 x 37 mm, stem length 53 mm 
Weight: approximately 150 g 
Material of the case: ABS 

Procedure of modification of transmitter adjustment: 

 

device adjustment is performed by means of the optional ATS-AC02 communication 
cable, connected to USB port of the PC. 

 

It is necessary to have installed configuration program Tsensor on the PC, It is free 
available at Atal B.V.. During installation please take care about installation of driver 
for  USB communication cable 

 

Connect ATS-AC02 communication cable to the PC. Installed USB driver detect 
connected cable and create virtual COM port inside the PC. 

 

Unscrew four screws of the device lid a remove the lid. If device is already installed to 
measuring system, disconnect leads from terminals 

 

Connect ATS-AC02 communication cable to the device. Display must light up, or at 
least must light up all symbols for one second (if LCD was switched OFF by program 
before).  

 

Run installed Tsensor program and select corresponding communication COM port (as 
described above). 

 

When new setting is saved and finished, disconnect the cable from the device, connect 
leads into its terminals and place the lid back to the device. 

Error states of the device 

Device continuously checks its state during operation. In case error is found LCD displays 

corresponding error code: 

Error 0 

First line displays „Err0“. 
Check sum error of stored setting inside device’s memory. Output value is < 3.8 mA. This error 
appears if incorrect writing procedure to device’s memory occurred or if damage of calibration data 
appeared. At this state device does not measure and calculate values. It is a serious error, contact 
distributor of the instrument to fix. 

Error 1 

Measured value is over upper limit of allowed full scale range. There is a reading „Err1“ on LCD 
display. Output value is about 24.5 mA. This state appears if measured temperature is higher than 
approximately 600°C (i.e. high non-measurable resistance of temperature sensor, probably opened 
circuit). 

Содержание TEA-101D

Страница 1: ...TEA 101D TRANSMITTER Programmable temperature transmitter with 4 20 mA output Instruction Manual ...

Страница 2: ...essible after unscrewing four screws and removing the lid Lace the cable through a gland at the case wall Connect the cable to terminals with respecting the signal polarity see figure Terminals are self clamping and can be opened by a suitable screwdriver For the opening insert the screwdriver to upper terminal hole and lever by him Do not remember to tighten glands and case lid with inserted pack...

Страница 3: ... Uo min Imax Rz where Uo min 9 V Imax approximately 20 mA Rz sensing resistor shunt Choice of optimal power voltage and load resistor for current loop area no 1 transmitter doesn t work correctly area no 2 optimal Uss and Rz area no 3 transmitter is working but it is possible to see undesirable warm influence ...

Страница 4: ...tice during info mode no measurement and no output current generation proceed The transmitter stays at info mode 15 s and then automatically goes back to measuring cycle Readings on LCD display C F Reading next to this symbol is measured temperature or error state of value Technical parameters Analog output Current loop with range from 4 to 20 mA Current output in case of error 3 8 mA or 24 mA Mea...

Страница 5: ...te virtual COM port inside the PC Unscrew four screws of the device lid a remove the lid If device is already installed to measuring system disconnect leads from terminals Connect ATS AC02 communication cable to the device Display must light up or at least must light up all symbols for one second if LCD was switched OFF by program before Run installed Tsensor program and select corresponding commu...

Страница 6: ...obably short circuit Error 3 There is a reading Err3 on LCD display upper line Error of internal A D converter appeared converter does not respond probably damage of A D converter No measurements proceed Output value is about 3 8 mA It is a serious error contact distributor of the instrument End of operation Device itself after its life is necessary to liquidate ecologically Technical support and ...