Atal TEA-101D Скачать руководство пользователя страница 2

2  

 

Instruction manual for use of TEA-101D transmitter 

Transmitter is designed for measurement of ambient air temperature at °C or °F. Measuring 

temperature sensor is non-removable instrument part. Measured temperature is displayed on LCD 
display. It is possible to switch OFF the LCD display. Transmitter is connected to circuitry by 
current loop. Please read instruction manual before the first device connection. 

All transmitter setting is performed by means of the PC connected via the optional  

communication cable (not included in delivery). Program 

Tsensor

 for transmitter setting is 

available at ATAL B.V.. Program enables to set measured range and on/off the LCD display. It 
supports make the adjustment of the device too. This procedure is described at file „

Calibration 

manual.pdf

“ which is installed commonly with the software. 

Device setting from the manufacturer 

Transmitter is set from the manufacturer to the following parameters: 

value at output I1:

 temperature, range 4 – 20 mA corresponds to -30 to +80 °C 

display:

 switched ON 

 

Modification of the setting is possible to do by means of the PC using procedure described 

at the end of this document. 

Installation of the transmitter 

Transmitter is designed for wall mounting. There are two mounting holes at the sides of the 

case. Don’t connect transmitter while power supply voltage is on. Interconnection terminals are 
accessible after unscrewing four screws and removing the lid. Lace the cable through a gland at the 
case wall. Connect the cable to terminals with respecting the signal polarity (see figure). Terminals 
are self-clamping and can be opened by a suitable screwdriver. For the opening, insert the 
screwdriver to upper terminal hole and lever by him. Do not remember to tighten glands and case 
lid with inserted packing after cables connecting. It is necessary for warranting of protection IP65. 

It is recommended to use shielded copper cable (e.g. SYKFY) with outside diameter of the 

cable must be from 3.5 to 8 mm, maximal length 1200m. The cable must be located at indoor rooms 
(probe is not protected for outdoor use). The cable should not be led in parallel along power 
cabling. Safety distance is up to 0.5 m otherwise undesirable induction of interference signals can 
appear. 

 
In the application where air flow is too low it is possible that measurement accuracy may be a 

bit lower (in decimals of °C) due to undesirable warm influence which develops in transmitter 
electronics because of its own power dissipation. Mechanical construction of the transmitter and 
working position is minimizing this effect, but in critical applications we recommend to use optimal 
value of load resistor Rz (see graph no.2 below). It minimizes power dissipation to minimal value. 
If Uss and Rz are set, it is possible to do it by inserting of suitable serial resistor into current loop at 
estimation device side. 

Electrical system (wiring) may do only worker with required qualification by rules in 

operation. 

 
 
 

Содержание TEA-101D

Страница 1: ...TEA 101D TRANSMITTER Programmable temperature transmitter with 4 20 mA output Instruction Manual ...

Страница 2: ...essible after unscrewing four screws and removing the lid Lace the cable through a gland at the case wall Connect the cable to terminals with respecting the signal polarity see figure Terminals are self clamping and can be opened by a suitable screwdriver For the opening insert the screwdriver to upper terminal hole and lever by him Do not remember to tighten glands and case lid with inserted pack...

Страница 3: ... Uo min Imax Rz where Uo min 9 V Imax approximately 20 mA Rz sensing resistor shunt Choice of optimal power voltage and load resistor for current loop area no 1 transmitter doesn t work correctly area no 2 optimal Uss and Rz area no 3 transmitter is working but it is possible to see undesirable warm influence ...

Страница 4: ...tice during info mode no measurement and no output current generation proceed The transmitter stays at info mode 15 s and then automatically goes back to measuring cycle Readings on LCD display C F Reading next to this symbol is measured temperature or error state of value Technical parameters Analog output Current loop with range from 4 to 20 mA Current output in case of error 3 8 mA or 24 mA Mea...

Страница 5: ...te virtual COM port inside the PC Unscrew four screws of the device lid a remove the lid If device is already installed to measuring system disconnect leads from terminals Connect ATS AC02 communication cable to the device Display must light up or at least must light up all symbols for one second if LCD was switched OFF by program before Run installed Tsensor program and select corresponding commu...

Страница 6: ...obably short circuit Error 3 There is a reading Err3 on LCD display upper line Error of internal A D converter appeared converter does not respond probably damage of A D converter No measurements proceed Output value is about 3 8 mA It is a serious error contact distributor of the instrument End of operation Device itself after its life is necessary to liquidate ecologically Technical support and ...

Страница 7: ...7 Notes ...