TEA-101D TRANSMITTER 

 

 

Programmable temperature transmitter with 4-20 mA output 

 
 
 
 
 
 
 

Instruction Manual

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание TEA-101D

Страница 1: ...TEA 101D TRANSMITTER Programmable temperature transmitter with 4 20 mA output Instruction Manual ...

Страница 2: ...essible after unscrewing four screws and removing the lid Lace the cable through a gland at the case wall Connect the cable to terminals with respecting the signal polarity see figure Terminals are self clamping and can be opened by a suitable screwdriver For the opening insert the screwdriver to upper terminal hole and lever by him Do not remember to tighten glands and case lid with inserted pack...

Страница 3: ... Uo min Imax Rz where Uo min 9 V Imax approximately 20 mA Rz sensing resistor shunt Choice of optimal power voltage and load resistor for current loop area no 1 transmitter doesn t work correctly area no 2 optimal Uss and Rz area no 3 transmitter is working but it is possible to see undesirable warm influence ...

Страница 4: ...tice during info mode no measurement and no output current generation proceed The transmitter stays at info mode 15 s and then automatically goes back to measuring cycle Readings on LCD display C F Reading next to this symbol is measured temperature or error state of value Technical parameters Analog output Current loop with range from 4 to 20 mA Current output in case of error 3 8 mA or 24 mA Mea...

Страница 5: ...te virtual COM port inside the PC Unscrew four screws of the device lid a remove the lid If device is already installed to measuring system disconnect leads from terminals Connect ATS AC02 communication cable to the device Display must light up or at least must light up all symbols for one second if LCD was switched OFF by program before Run installed Tsensor program and select corresponding commu...

Страница 6: ...obably short circuit Error 3 There is a reading Err3 on LCD display upper line Error of internal A D converter appeared converter does not respond probably damage of A D converter No measurements proceed Output value is about 3 8 mA It is a serious error contact distributor of the instrument End of operation Device itself after its life is necessary to liquidate ecologically Technical support and ...

Страница 7: ...7 Notes ...