Prepare  incoming  black  iron  gas  line  with 

Teflon tape or pipe joint compound (check with 

local codes as to the use of Teflon tape). Com-

pounds used on threaded joints of gas piping 

shall be resistant to the action of propane/LP 

and should be applied lightly to ensure excess 

sealant does not enter the gas line.
Complete your gas installation by connecting 

the incoming gas line to the appliance regula-

tor. Secure all joints tightly with wrench but do 

not overtighten. If a flexible gas line is used, 

take care not to kink the connector.

 WARNING: All gas piping 

and connections must be tested 

for leaks after the installation is 

completed. After ensuring that 

the manual shutoff gas valve is 

open, apply a soap and water 

solution to all connections and 

joints. If bubbles appear, leaks 

can be detected and corrected. 

DO NOT USE OPEN FLAME FOR 

LEAK  TESTING  AND  DO  NOT 

OPERATE ANY APPLIANCE  IF 

A LEAK IS DETECTED.

INSTALLATION

Continued

GAS SUPPLY TESTING

Note: This section is intended as a guide for 

qualified  technicians  installing  gas  to  this 

vent-free firebox.

  CAUTION:  Do  not  connect 

vent-free appliance before pres-

sure testing gas piping. Damage 

to gas valve may result and an 

unsafe condition may be caused.

The appliance and its’ individual shutoff valve 

must be disconnected from the gas supply 

piping system during any pressure testing of 

that system at test pressures in excess of 1/2 

psig (3.5 kPa).
The appliance must be isolated from the gas 

supply piping system by closing manual shut-

off valve during any pressure testing of the gas 

supply piping system at test pressures equal 

to or less than 1/2 psig (3.5 kPa).

Figure 15 - Locating Electrical 

Connection and Gas Connection on 

Either Side of Fireplace

HARD-WIRING FIREBOX

This model can be hard-wired to the duplex 

outlet  located  inside  the  firebox  bottom  if 

desired. This allows the blower accessory to 

be plugged into the duplex outlet.

NOTICE: A qualified electrician 

must connect electrical wiring to 

duplex outlet for built-in instal-

lation. Follow all local codes. In 

absence of local codes follow 

The National Electric Code ANS/

NFPA 70.

ELECTRICAL INSTALLATION

A model GA3500A blower system assembly 

is available for use with the vent-free firebox 

as  an  optional  accessory.  This  blower  is 

designed to be installed on either side of 

the firebox, when provisions for a 120 VAC 

supply connection are made at either end 

of the cabinet. Use of a blower system other 

than those manufactured by INNOVATIVE 

HEARTH PRODUCTS voids the warranty.
Electrical  connections  are  made  within  the 

receptacle with wires that are routed through 

the bushing provided (see Figure 15). The re-

ceptacle may be relocated to either side, when 

necessary. However, the cover plate must be 

replaced over the unused access point. Be 

certain to properly ground the vent-free firebox 

using the green grounding wire.

Note: A 120V supply connection to the leads 

Cover 

Plates

Electrical 

Connection 

Access Hole

Gas Connection 

Access Hole

Содержание TaurusPFZ

Страница 1: ...xplosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas s...

Страница 2: ...Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting SAFETY This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer This firebox has been tested under Z21 91b 2007 for use with approved ANSI Z2...

Страница 3: ... cause pilot outage 12 Do not use the firebox if it has been un der water due to the shock hazard that could result with the blower accessary if installed in place 13 Provide adequate clearances around air openings Due to high temperatures the appliance should be located out oftrafficandawayfromfurniture and draperies Do not place clothing or other flammable material on or near the appliance Never...

Страница 4: ...re you bought firebox 3 Check appliance for any shipping damage If appliance is damaged call INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 for replacement parts before returning to dealer NOTICE The firebox identifica tionlabel includingmodelnum ber serial number clearances etc islocateddirectlyabovethe brick liner and under the heat shield See Figure 20 page 16 PRODUCT FEATURES OPERATION This fire...

Страница 5: ...box will be located Allow for wall and ceiling clearances see Installa tion Clearances page 9 2 Everything needed to complete installation 3 This model CANNOT be installed in a bedroom or bathroom 4 Proper air for combustion and ventilation 5 Consider a location where heat output would not be affected by drafts air condi tion ducts windows or doors 6 A location that minimizes modifications on exis...

Страница 6: ...y provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the out side atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed...

Страница 7: ... vents to the outdoors Example Gas water appliance ___________ Btu Hr Gas firebox logs __________ Btu Hr Total __________ Btu Hr AIR FOR COMBUSTION AND VENTILATION Continued 40 000 39 000 79 000 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used ________ Btu Hr maximum the space can support ________ Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr max...

Страница 8: ... 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include at tics and crawl spaces Follow the National Fuel Gas Code ANS Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo ...

Страница 9: ... provide greater clearances from floor ceiling and adjoining wall Carefully follow the instructions below This will ensure safe installation Minimum Wall and Ceiling Clearances A Clearances from edge of liner to any combustible wall should not be less than 8 see Figure 5 B Clearances from top of firebox opening to the ceiling should not be less than 42 INSTALLATION Continued C When the firebox is ...

Страница 10: ... installation of this firebox involves installing firebox into a framed in enclosure This makes the front of firebox flush with wall If installing a mantel above the firebox you must follow the clearances shown in Figure 7 Follow the instructions below to install the Figure 7 Minimum Mantel Clearances for Built In Installation 4 Min 43 3 4 Min 36 Min to Facing Wall 22 3 4 Min Facing Wall Wallboard...

Страница 11: ...ouvered slots on the front of the firebox WARNING Use only non combustible mortar or adhe siveswhenoverlappingthefront facing with noncombustible facing material WARNING Do not fill the spaces around the firebox with insulation or other materials WARNING Framing may be placed or rest against fireplace spacer however framing must never be notched WARNING Do not alter cut or modify fireplace spacers...

Страница 12: ...ay be run from the regulator to the incoming 1 2 NPT black iron gas line You may also route the incoming 1 2 NPT black iron gas line directly to the appliance regulator Remove the gas line cover plate from the vent free firebox s outer surround and route Figure 11 Installing Gas Line and Manual Shutoff Valve Manual Shutoff Valve is Located Under Firebox Floor on Either Side Gas Line Installed Thro...

Страница 13: ...sures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Figure 15 Locating Electrical Connection and Gas Connection on Either Side of Fireplace HARD WIRING FIREBOX This model can be hard wired to the duple...

Страница 14: ...ating air passageways of the appliance be kept clean WARNING Children and adults should be alerted to the hazardsofhighsurfacetempera tures and to stay away to avoid burnsorclothingignition Young children should be carefully supervised when they are in the same room as the appliance For lighting and operating this vent free firebox please refer to the vent free gas logs manufacturer s instruction ...

Страница 15: ...ioning purchase date Usually we will ask you to return the part to the factory TECHNICAL SERVICE You may have further questions about installa tion operation or troubleshooting If so contact INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 Whencallingpleasehaveyourmodel and serial numbers of your appliance ready You can also visit the INNOVATIVE HEARTH PRODUCTS web site at www IHP US com ACCESSORY Pur...

Страница 16: ... com 126688 01A 16 PARTS MODEL TAURUSPFZ2 These items are used on both sides of fireplace 8 15 17 17 17 7 1 7 2 7 3 2 17 11 17 17 12 6 16 13 10 5 17 17 15 16 4 16 16 6 16 15 17 17 18 Typ Typ Typ 8 17 17 9 14 16 1 3 ...

Страница 17: ...acer 4 5 26731 Deflector Hood 2 6 26740 Nailing Flange 12 7 1 02013 Side Refractory Brick Liner 1 7 2 02014 Bottom Refractory Brick Liner 1 7 3 02036 Bottom Refractory Brick Liner 1 8 24007 Side Refractory Retainer 2 9 12125 Screen 4 10 26752 Extruded Louver 2 11 26733 Lower Door Panel 2 12 14200 Receptacle 1 13 21171 Access Hole Cover 3 14 12126 Screen 1 15 26771 Extruded Louver End 1 16 11164 Sc...

Страница 18: ... flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive tempera...

Страница 19: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ___________________________ Keep receipt for warranty verification ...

Страница 20: ...126688 01 Rev A 02 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126688 01 ...

Отзывы: