Astria.us.com
125160-01_D
12
NOTE:
It is required that ember protector strips must be laid on the
fiber of the non-combustible raised platform (see Figure 12). These
are included with the Metal Base accessory.
WARNING: Hearth extension is to be installed
only as shown in Figure 12.
MANTEL AND MANTEL SHELF CLEARANCES
As with any radiant heat fireplace, the Grand Meridian fireplaces
must comply with building code safety clearances, per units that
have openings of 6 sq. ft. or greater. For Mantel clearances see Fig-
ure 5, page 8. Walls that Adjoin – Safety codes and all practical
outlooks insist that your fireplace cannot be installed closer than 2
ft. to any walls in the room the fireplace is housed in or to any walls
of adjoining rooms.
Caution in Regards to Combustibles – If any part of the fireplace
or objects in the room (curtains, rugs, paint, cushions, etc.) start
to show warping or discoloration due to heat from the fireplace,
it is time to take immediate action. Do not use the fireplace until
you have figured out how to address the problem. You are facing a
potential fire hazard. IHP cannot be responsible for the make-up of
material on the exterior of the fireplace you have chosen, nor can
IHP be held responsible for the materials in a room that may be
responding negatively to heat. However, in almost all cases, there is
a solution to the problem, either by making adjustments to airflow
or the modifications to the room itself.
HEARTH EXTENSION
Where the flooring material at the opening of the fireplace is
combustible, it is required that the hearth extension be covered with
a non-combustible material. All hearth extensions must be made of
code-rated, non-combustible materials such as tile, brick, marble,
concrete or stone. The extension should be set flush against the
front of the fireplace front and measure 20" minimum at the front
and 12" minimum beyond the sides of the fireplace opening as
shown in Figures 8 and 9 (page 10). These relative dimensions are
also covered by code.
If a raised hearth extension is being installed, it must be constructed
of non-combustible material and any material under the structure
must also be non-combustible.
If using a raised hearth or metal base plate, note that a combustible
wood header must be no closer than 2" to the top of the dome (see
Figure 6, page 9).
ATTENTION:
You will note that there will be a gap between the
fireplace front and the extension of the non-combustible hearth
material. Be certain that you seal this with non-combustible
material.
These Grand Meridian Fireplaces have been designed with
clearance to combustible floors as indicated in Page 8. Cover any
part of the combustible floor system left exposed with 1” (one
inch) thick ceramic fiber insulation rated up to 2,100° F.
ATTENTION:
It is critical to abide by the clearances listed in this
manual for all components specified as it allows for movement of
hot air from the fireplace into interior areas of the chimney chase.
Also, be certain that the chimney system be installed as stated be-
low.
Prior to starting the installation, check with local, regional or
state codes for any restrictions or required permits regarding your
fireplace installation.
Figure 12 - Hearth Extension
Seal Gap
Fireplace Front
Fireplace Front Raised
Hearth
Fireplace Front
Elevated
Ember Protector
Seal Gap
Ember Protector
Ember Protector
Hearth
Extension
Hearth
Extension
Hearth
Extension
PRE-INSTALLATION PREPARATION
Continued