The space in the example is a confined space because the actual Btu/

Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:

A.

  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. See Ventilation Air 

From Inside Building.

B.

 Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.

  Install a lower Btu/Hr appliance, if lower Btu/Hr size makes room 

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no 

additional fresh air ventilation.

 WARNING: If the area in which the appliance may 

be operated does not meet the required volume for 

indoor combustion air, combustion and ventilation air 

shall be provided by one of the methods described in 

the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

 

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 

12" of the floor on the wall connecting the two spaces (see options 

1 and 2, Figure 2). You can also remove door into adjoining room 

(see option 3, Figure 1). Follow the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54, Air for Combustion and Ventilation for required size 

of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and 

one within 12" of the floor. Connect these items directly to the out-

doors or spaces open to the outdoors. These spaces include attics 

and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

NFPA  54,  Air  for  Combustion  and  Ventilation  for  required  size  of 

ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

AIR FOR COMBUSTION AND VENTILATION  

Continued

Figure 3 - Ventilation Air from Outdoors (Appliance may differ 

from actual model)

Figure 2 - Ventilation Air from Inside Building (Appliance may 

differ from actual model)

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Содержание london lights

Страница 1: ...is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 5 of this manual WARNING If the information in these i...

Страница 2: ...en people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes Make certain you read and understand all warnings Keep this manual for reference It is y...

Страница 3: ...ot convertible for use with other gases 2 Always keep a fire extinguisher CLASS B near the appliance 3 Never refill appliance fuel reservoir when appliance is operating or still hot 4 This appliance s...

Страница 4: ...e vent ing There is no heat loss out a vent or up a chimney Heat is generated by real flames This appliance is designed for vent free operation It has been tested and approved to UL 1370 standard for...

Страница 5: ...u must provide additional fresh air See Ventilation Air From Outdoors page 6 If your home does not meet all of the three criteria above proceed to Determining Fresh Air Flow For Appliance Location Con...

Страница 6: ...nt openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see option 3 Fig...

Страница 7: ...CES WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoining wall Carefully follow the instructions below This will ensure safe instal lation CLEA...

Страница 8: ...wn in this manual INSTALLING REMOVING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 7 2 Tighten screws securing hood to fireplace 3 To remove reverse the...

Страница 9: ...Astria US com 127331 01A 9 INSTALLATION Continued 18 3 4 37 3 4 40 3 4 44 3 16 55 3 16 16 1 4 55 3 16 47 1 8 1 1 2 22 7 16 1 11 16 4 13 16 13 1 8 1 14 1 4 5 8 5 8 Figure 8 LONDON LIGHTS Dimensions...

Страница 10: ...Reservoir Figure 9 Filling the Fuel Tank Reservoir FILLING THE FUEL TANK RESERVOIR 1 Open bottom access panel Note Use the index finger of both hands when opening access panel by inserting them thru...

Страница 11: ...y periodically Replace battery if needed by unscrewing battery compartment cap see Figure 10 TO TURN OFF APPLIANCE 1 Slide shut off plate fully closed by pushing plate handle in com pletely and make s...

Страница 12: ...rd you Insert bottom flange of screen door into the retaining channel at the bottom of firebox see Figure 12 Make sure door is center with firebox opening 2 Tilt top of door up toward top of firebox 3...

Страница 13: ...Astria US com 127331 01A 13 CLEANING AND MAINTENANCE Continued Figure 14 Glass Nuggets Installation Nuggets Pan Burner Fuel Tray Access Door...

Страница 14: ...FP1 or FP2 Denatured Ethanol only Note You can purchase these types of ethanol fuel by contacting PHARMCO AAPER at 800 456 1017 or www pharm coaaper com 5 Slide shutoff plate fully open 6 Wait at leas...

Страница 15: ...so contact IHP at 1 800 655 2008 When calling please have your model and serial numbers of your ap pliance ready You can also visit our web site at Astria US com ACCESSORIES NOTICE All accessories ma...

Страница 16: ...yle 3 16 1 11 126478 01 Fuel Tank Release Rod 1 12 126480 01 External Retaining Ring 1 13 17373 Spring Tank Release 1 14 111733 01 Washer Black M6 1 15 127000 01 Fuel Supply Line 9 5 1 16 126474 01 Cl...

Страница 17: ...6 Screw 8 32 x 1 2 10 126559 01 Switch Momentary 1 11 126472 01 Bracket Spark Ignitor 1 12 11201 8 32 Hex Nut 2 13 125763 01 Bracket corner Wall 4 14 125813 02 Wall Side Porcelain 2 15 125814 01 Wall...

Страница 18: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Страница 19: ...produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d d...

Страница 20: ...tion tag ____________________ Date Purchased _______________________ Keep receipt for warranty verification Innovative Hearth Products reserves the right to make changes at any time without notice in...

Отзывы: