![Astria Fireplaces Alpha32ZEN Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/astria-fireplaces/alpha32zen/alpha32zen_installation-and-operation-instructions_2990876008.webp)
Astria.us.com
900720-00E
8
Figure 4 - Ventilation Air from Outdoors
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Follow the
National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent open-
ings: one within 12" of the ceiling and one within
12" of the fl oor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air
for Combustion and Ventilation
for required size of
ventilation grills or ducts.
AIR FOR COMBUSTION AND VENTILATION
Continued
IMPORTANT
:
Do not provide openings for inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic
will activate the power vent.