PROHEAT II SERIES · HEAT PUMP AIR/WATER SYSTEM
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
ENGLISH
Pag: 23
F46
Alarm delay time phase protection
failure
0 – 30
2
S
F47
Phase failure alarm delay time
0 – 30
2
S
Autostart
F49
If there is a power failure, when
the power is restored, PROHEAT II
device is reset in the same
condition.
0 – 1
1
1
=
Enable
0=Not enable
Water pump
and fan
F50
Water Pump Select
0 – 1
1
0: water pump is not enable
1: water pump is enable
Contact Voltage = 220v
F51
Water pump starts time before
compressor starts
1 – 10
3
min
F52
Water pump stops time after
compressor stops
0 -10
3
min
F53
Water pump start time
0 – 99
60
min
Check water temperature
F54
Water pump run time
0 – 99
5
min
F55
Exhaust Temp.protection
90–135
115
°
C
Compressor Exhaust Temp.
F56
Water flow switch
0 - 1
1
1
:
Enable
0
:
Not enable
F57
Fan overload
0 - 1
1
1
:
Enable
0
:
Not enable
Alarm and
probe
calibration
F58
Buzzer alarm sound
duration
0.1 – 10.0
0
0: No alarm sound
606: Alarm sound is always
on until pressing any key
F59
Min. Ambient Temp. of starting
the Electrical heater
-10 – 20
12
°
C
If electrical heater is available
F60
Over high temperature difference
between water inlet and water
outlet failure
0 – 20
3
°
C
F61
Water inlet Temp sensor
adjustment.
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F62
Water outlet Temp sensor
adjustment
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F63
1 # Calibration temperature
defrost probe 1
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F64
2 # Calibration temperature
defrost probe 2
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F65
Ambient Temp sensor adjustment
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F66
Compressor 1 exhaust Temp
sensor adjustment
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F67
Compressor 2 exhaust Temp
sensor adjustment
-20 – 20
0
°
C
Adjust the temperature sensor
(calíbrate)
F68
Calibration temperature probe
suction compressor 1
-20 – 20
0
ºC
Adjust the temperature sensor
(calíbrate)
F69
Calibration temperature probe
suction compressor 2
-20 – 20
0
ºC
Adjust the temperature sensor
(calíbrate)
Electronic
expansion
valve
(OPTIONAL)
F70
Electronic expansion valve
0 – 1
0
-
1
:
enable, 0
:
disabled
F71
Refrigerant
0 – 1
0
-
0
:
R-410-A
1
:
R-407-C
F72
Maximum output voltage
(Pressure Sensor)
0.5 – 5.0
4.5
V
Maximum pressure sensor output
voltage for scaling.
F73
Max. Sensor pressure
0 – 5
4.6
MPa
Max. Sensor pressure for scaling
F74
Initial valve position cool mode
100 – 480
240
Steps
F75
Initial valve position heat mode
100 – 480
240
Steps
F76
Overheating setting time
0 – 120
30
S
F77
Fine tuning steps
0 – 10
1
Steps
EEV adjust steps
F78
Middle tuning steps
0 – 10
3
Steps
EEV adjust steps
F79
Coarse tuning steps
0 – 10
6
Steps
EEV adjust steps
F80
Target overheating in heat mode
3 – 20
6
ºC
F81
Objective overheati in cold mode
3 – 25
10
ºC