Input Wiring

Each input on the R8 has an “IN” 

terminal and a “GND” terminal.

When using a NO relay contact to activate the 

input, the contact is placed across these terminals.

To use a DC ground or an open collector (transistor)

as an input, connect the ground/open collector 

to the “IN” terminal to activate the input. 

Note that the input source must be common 

grounded with the R8 board’s power source.

Output Wiring

Each output on the R8 has “NC”, “C”,

“NO”, and “COM” terminals.

When set for a dry contact output, the C, NC, 

and NO terminals may be used as any relay 

would. C to NC will have a connection when 

the red LED for the zone is not lit. C to NO will

have a connection when the red LED is lit.

NOTE:

 To set the output as a dry contact, the 

yellow and black jumpers for the zone must be 

removed and the output diodes must be cut.

When set for a voltage output, the

terminal use is as follows:

 ›

COM –

 This is the negative DC Common 

for the device being powered

 ›

C – 

This terminal always has positive voltage, regardless

of the relay state. This terminal may be used to 

power auxiliary devices such as REX or readers.

 ›

NC –

 This output has positive voltage 

when the relay is NOT ACTIVE. This 

terminal is used for FAIL SAFE locks

 ›

NO – 

This output has positive voltage when the relay 

is ACTIVE. This terminal is used for FAIL SECURE locks

NOTE:

 Other Securitron Power Boards (not part of 

AQL series) use C as a negative DC common.

Power Control Dry 

Contact Output 

The outputs of the R8 have built-in reverse protection 

diodes. If a delay in lock release is present or if the zone is 

being used as a dry contact output, the diode from that 

zone may be removed from the circuit as shown below.

NOTE:

 Only remove the diodes from 

outputs requiring their removal

Diode Removal

The diodes on the R8 are on the top side of the board 

between the output terminals and the edge of the 

board. To remove the diode from the output circuit, 

simply cut the exposed diode lead for the desired 

output zone - leave the diode body soldered to the pcb.

GND

GND

GND

GND

1

2

3

4

GND

GND

GND

GND

5

6

7

8

INPUT 1– 4

INPUT 5 –8

GND

GND

GND

GND

GND

GND

GND

GND

B2
BR

B1

IN1

IN2

IN3

IN4

IN8

IN7

IN6

IN5

NC C N0 COM

NC C N0 COM

OUTPUT - 1

OUTPUT - 2

NC C N0 COM

NC C N0 COM

OUTPUT - 1

OUTPUT - 2

NC C N0 COM

NC C N0 COM

OUTPUT - 1

OUTPUT - 2

NC C N0 COM

NC C N0 COM

OUTPUT - 1

OUTPUT - 2

INPUT 1 – 2

INPUT 3 – 4

INPUT 5 – 6

INPUT 7 – 8

Отзывы: