ASSA ABLOY Hospitality
66 8003 016-3
To set up the online network
The online network for the above example looks as in
Figure C22
. The three
thermostats 1021, 1022 and 1023 must be set up under the same parent in the
network, i.e. be set up in the same PAN (
personal area network
). To set up the
network, follow the steps below:
1. Double click on
SysMon.exe
in the Visionline installation folder to open
SysMon (
System Monitor
) which is used for managing the online network.
2. Log on to SysMon; go to
File/Log on
and enter user ID and password. At
'Operator card', choose the applicable card encoder and click
Enter
.
3. Go to
View/Online Network
to show the
Online Network
tree.
4. Install the gateway; see
User manual Online option
for details.
5. Initialize
thermostat 1021
with "regular parameters", i.e. all parameters except
for those related to suite. To do this, use the
Initialize
alternative in Orion
Service but leave the
Suite settings
empty. See
Daily use manual Orion EMS
for details about
Initialize
.
6. Connect
thermostat 1021
to the gateway; see
chapter 5
for details.
7. Connect
motion sensor 1021
to
thermostat 1021
; see
chapter 5
for details.
8. Connect
lock 102
to
thermostat 1021
; see
chapter 5
for details.
9. Repeat steps 5-7 for the devices in rooms 1022 and 1023 respectively.
10.Initialize
thermostat 1021
with suite settings; click
here
for details.
11.Initialize
thermostat 1022
with suite settings; click
here
for details.
12.Read out the thermostat status for
thermostat 1021
; click
here
for details.
13.Read out the thermostat status for
thermostat 1022
; click
here
for details.
14.See
Figure C32
for a picture of the final
Online Network
tree.
Figure C22