53
Function and operation
EN
Control and status messages
The
electric multi-point lock 819N
can be actuated in different ways.
The
electric multi-point lock 819N
can
be actuated via the OneSystem IO module N5950 (separate instruc-
tions D00852).
The
electric multi-point lock 819N
can be actuated without an additional control unit
(“Connection
(without OneSystem IO module N5950)”, page 61).
A control input is available for unlocking without
an additional control unit. Status messages are not sent.
Fail-unlocked and fail-locked in the event of a power failure
The
electric multi-point lock 819N
can be operated in
fail-locked
or
fail-unlocked
mode. The setting takes
place via DIP switches on the lock
(“Connection (without OneSystem IO module N5950)”, page 61)
.
This results in different function states in the event of a power failure.
In the
fail-locked
version, the outer door handle is disengaged when there is no electrical voltage supply. In
the event of a power failure, the outer door handle is disengaged, the door can only be accessed on the
controlled side (usually the outside) via locking cylinders.
In the
fail-unlocked
version, the outer door handle is engaged when there is no electrical voltage supply. In
the event of a power failure, the outer door handle is engaged, the door can be accessed on both sides.
This function may be necessary for free access for the fire brigade and rescue services in an emergency
situation, for example.
Behavior when switching on, switching off and in the event of a power failure
The
electric multi-point lock 819N
has an electric buffer, which enables a defined coupling state to be
entered in the event of a power failure.
The electrically connected lock (“Electrical connection”, page 61) is switched on by switching on the
voltage. The lock is ready for operation after 10 seconds. No change in the coupling state is possible before
this time (“No reaction to control signal”, page 73).
After the voltage is switched off or in the event of a power failure, the electric buffer discharges completely
after 30 seconds.
Carrying out a voltage reset or switching the DIP switch
1
Switch off the power supply.
2
Wait at least 30 seconds.
3
Where necessary, switch the DIP switch.
4
Switch on the voltage supply again.
5
Wait at least 10 seconds.
You have carried out a voltage reset.
with
OneSystem IO module
N5950
without
OneSystem IO module
N5950
Fail-locked
Fail-unlocked
Содержание OneSystem 819N
Страница 49: ...49 Notices EN Fig 2 OneSystem electric multi point lock 819N Fig 3 Rebate gap B A 2 3 4 5 6 7 8 9 1...
Страница 85: ...85 Avis FR Fig 2 Serrure multipoint lectrique 819N OneSystem Fig 3 Jeu de fonctionnement B A 2 3 4 5 6 7 8 9 1...
Страница 121: ...121 Indicazioni IT Fig 2 Serratura elettrica multipunto 819N OneSystem Fig 3 Luce di funzionamento B A 2 3 4 5 6 7 8 9 1...
Страница 187: ...187 Abmessungen Dimensions Dimensions Dimensioni Afmetingen DE EN FR IT NL...