CL33600 Series Cylindrical Lock

5

Copyright © 2017 Corbin Russwin, Inc. All rights reserved.

Reproduction in whole or in part without the express written  

permission of Corbin Russwin, Inc. is prohibited.

Product

8 PIN CONNECTION

4 PIN CONNECTOR

1-Black

2-Red

3-White

4-Green

5-Orange

6-Blue

7-Brown

8-Yellow

9-Violet

10-Gray

11-Pink

12-Tan

ACCESS CONTROL DEVICES: ML20600 x M802, ElectroLynx wire Color / Function assignments

12VDC

Reader Power

WIE-

GAND

WIE-

GAND

RX (NO)

RX (COM)

EGND

LED

12 OR 24 VDC

(LOCK RELAY

DPS (NC)

DPS 

(COM)

Corbin Russwin 

Access 600 

ML20600 x M802

NEG

POS

DATA_1

DATA_0

RX

RX

EGND

REF.
DIA-

GRAMS

NEG

POS

DPS

DPS

PIN8 (Yellow – LED)

PIN 6 (Blue – RX COM)

PIN 4 (Green – Data 0)

PIN 2 (Red – Reader POS)

PIN 1 (Black – Reader NEG)

PIN 3 (White – Data 1)

PIN 5 (Orange – RX NO)

PIN 7 (Brown - EGND)

PIN 4 (Tan – DPS)

PIN 2 (Gray – Lock POS)

PIN 1 (Violet – Lock NEG)

PIN 3 (Pink – DPS)

6) Wiring Diagrams

Reader LED Configuration

The Access 600 Series reader can be configured for (3) modes of LED  

operation. Call 1-800-810-WIRE for details. 

Mode 1:

•  Red LED ‘ON’ when powered.
•  Presenting a valid credential causes LED to ‘FLICKER’  

   green and return to red state.

Mode 2:

•  Green LED “ON” when powered.
•  No Flicker after presenting valid valid credential.

Mode 3:

•  EAC Panel controls LED operation.
   Note: Control of LED is a function of the EAC panel equipment (i.e. relay) to toggle between                   

             green and red.
   Note: When LED wire is tied directly into EAC panel relay, no AC signals should be applied on  

             wire or door reader performance will be impacted.

Note: LED wire must be connected to circuit GROUND of 

the system’s power supply. 

Wire from EAC panel to door must be shielded with drain terminated at EAC  panel controller

Total 

One-Way  

Length of  

Wire Run (ft)

Load Current @ 12VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

20

18

16

14

14

12

12

10

150

18

16

14

12

12

12

10

200

16

14

12

12

10

10

250

16

14

12

10

10

10

300

16

12

12

10

10

400

14

12

10

500

14

10

10

750

12

10

1,000

10

1,500

10

Wire Gauge Charts

Total 

One-Way  

Length of  

Wire Run (ft)

Load Current @ 24VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

24

20

18

18

16

16

14

12

150

22

18

16

16

14

14

12

10

200

20

18

16

14

14

12

12

10

250

18

16

14

14

12

12

12

10

300

18

16

14

12

12

12

10

400

18

14

12

12

10

10

500

16

14

12

10

10

750

14

12

10

10

1,000

14

10

10

1,500

12

10

Содержание Corbin Russwin Access 600 CL33600 TCRNE1 M802

Страница 1: ...r Please read these instructions carefully to prevent missing important steps Please Note Improper installations may result in damage to the lock and void the factory warranty Important The accuracy o...

Страница 2: ...talla tion This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications...

Страница 3: ...or key retracts latch Inside lever produces REX request to exit signal Fail safe or fail secure operation must specify UL fire listed Wire from EAC panel to door must be shielded with a drain Drain te...

Страница 4: ...ies Cylindrical Lock Copyright 2017 Corbin Russwin Inc All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited 4 Product Illustr...

Страница 5: ...ed Presenting a valid credential causes LED to FLICKER green and return to red state Mode 2 Green LED ON when powered No Flicker after presenting valid valid credential Mode 3 EAC Panel controls LED o...

Страница 6: ...3600 Series Lock Patent Pending Standard Application Shown For Alternative Applications Contact 1 800 810 WIRE 9473 Reader Electronics Requires 12VDC Filtered and Regulated READER NEG Black 1 READER P...

Страница 7: ...Inward LH Left Hand Reverse Bevel Hinges Left Open Outward LHRB Right Hand Hinges Right Open Inward RH Right Hand Reverse Bevel Hinges Right Open Outward RHRB 1 Verify Hand and Bevel of door Illustra...

Страница 8: ...ten permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continued 3 Install Latch Bolt with beveled bolt facing the strike using two 8 x 3 4 combination screws Optional Strike B...

Страница 9: ...e latch engages lock body as shown Fig 5 IMPORTANT Door must remain open during installation Use door stop Fig 5a Detail Outside Face of Door 6 Install Inside Spring Cassette a Feed lock body wires an...

Страница 10: ...bin Russwin Inc All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continued 7 Installation and...

Страница 11: ...de Reader Escutcheon a Install exterior gasket if this is an exterior door Fig 8a b Insert reader assembly and route wires through door c Install two 8 32 x 1 3 4 flat head screws through mounting pla...

Страница 12: ...nk N A 1 Black PWR NEG 3 White DATA 1 5 Orange RX NO 7 Brown EGND 2 Gray Lock Pos Solenoid pos 4 Tan N A 2 Red PWR POS 4 Green DATA 0 6 Blue RX COM 8 Yellow LED 11 Install Inside Escutcheon Lever and...

Страница 13: ...has been successfully completed according to proper application a Turn power ON b Verify LED located on reader is ON red or green depending on reader configuration refer to reader LED configuration c...

Страница 14: ...Copyright 2017 Corbin Russwin Inc All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited...

Отзывы: