1004935-US-1.0

Issue 2008-11-13

13

5.4.5

Sensor Monitoring

Monitoring can be selected through a function selector jumper (Presence Sensor Moni-
toring).

Test of Presence Detection is performed before opening. Test of Presence Impulse is
performed before closing. The Master Sensors are tested first and the slave sensors
are tested when the answer is received from Master Sensors.

If sensor test is 

not

 performed successfully the door will enter Manual Mode and

report sensor error. The sensor test will continue during manual mode.

It is only possible to monitor sensors with a normally closed (NC) output. 

If the sensor error disappears during manual mode the door will re-enter automatic
mode again. 

5.4.6

Overhead Presence Detection (OPD) 

OPD impulse will prevent a closed door from opening and an open door from closing. 
A moving door will ignore the OPD input. The OPD will be active 6 seconds after the
door has started to close. If a home switch is installed, the OPD will be active as soon
as the door is closed.

OPD can be selected through a function selector jumper (Sensor type OPD/Mat).

5.4.7

Mat Safety

Mat safety impulse will prevent a closed door from opening and an open door from
closing.

No impulses are accepted during closing if mat is activated.

Mat safety can be selected through a function selector jumper (Sensor type OPD/
Mat).

5.4.8

LockOut 

LockOut is used to ignore the OPD sensor during opening and closing. Output will be
low (0 V DC) when the door is considered closed, high during opening and open and
toggling when the door is closing.

LockOut output will be low (0 V DC) when the door is manually opened.

5.4.9

Program selector 

Program Selector PS-4C can be connected to the EXB. 

The PS-4C, compared to PS-3B, has a fourth position EXIT that will make the CSDB
ignore the outer impulse device.

Presence sensors are enabled in all Program Selector settings but not when Kill Mode
has been activated.

Содержание Besam PowerSwing CSDB

Страница 1: ...ASSA ABLOY the global leader in door opening solutions 1004935 US 1 0 Issue 2008 11 13 ILL 01558 Besam Swing Door Operator PowerSwing CSDB Installation and Service Manual...

Страница 2: ...e the sole property of ASSA ABLOY Entrance Systems AB Copying scanning alter ations or modifications are expressly forbidden without the prior written consent of the applicable company within ASSA ABL...

Страница 3: ...specifications 7 5 How the PowerSwing works 8 6 Models 14 7 Part identification 15 8 Options 16 9 Pre Installation 21 10 Mechanical installation 24 11 Electrical Connection 32 12 Start Up 36 13 Cover...

Страница 4: ...1 13 1004935 US 1 0 1 Revision Following pages have been revised Page Revision This is the first version of Installation and Service Manual for Swing Door Operator PowerSwing CSDB No 1004935 US 1 0 Is...

Страница 5: ...ence in a residential installation However there is no guarantee that interference will not occur in a particular installa tion If this equipment does cause interference to radio or television recepti...

Страница 6: ...nd is suitable for single or double doors fitted with butt hinges or pivots It can also be installed on the door leaf The motor oil pump and hydraulic unit are combined into a compact unit mounted alo...

Страница 7: ...ed max door weight Arm system PUSH 550 lb for door leaf width 63 Arm system PULL 220 lb for door leaf width 55 Higher door weights on request Standards The PowerSwing complies with ANSI BHMA A156 10 A...

Страница 8: ...g angle is reached The open position is held by a hydraulic valve 5 2 Closing The spring closing starts when the hold open time has expired Before reaching the fully closed position the speed is reduc...

Страница 9: ...adjusted between 0 to 30 sec FS 2 OFF factory setting FS 3 OFF factory setting TB2 11 and 13 TB2 11 and 13 TB2 11 and 13 6 24 V AC DC CSDB No PS OFF AUTO EXB OFF OFF EXB EXIT EXIT EXB AUTO AUTO EXB O...

Страница 10: ...pening angles up to 120 When the Open Limit Switch is activated the motor will stop If the open limit switch is not activated the motor will stop 10 seconds after an activation impulse is received If...

Страница 11: ...e To prevent the thicker door panels from jamming a delay of 0 5 sec can be selected through Function Selector FS6 Slave Delay A Home Switch is recommended to prevent an open delay if a activation imp...

Страница 12: ...ulse is ignored when home impulse is active Presence impulse is ignored if the door is manually opened Presence impulse is not ignored if the door is opened with Push to Go The input can be either nor...

Страница 13: ...nput The OPD will be active 6 seconds after the door has started to close If a home switch is installed the OPD will be active as soon as the door is closed OPD can be selected through a function sele...

Страница 14: ...The product is delivered complete with back plate control unit end plates and cover Length including end plates L 51 or 88 Pushing arm system shown 6 2 Double Operator Consult Product Order form for...

Страница 15: ...116 Extension unit EXB see page 18 6 655600 Capacitor 25 F 120 V complete 7 1004117 3 position switch PS 3B for CSDB see page 18 8 1003542 Top end plate 9 655614 Limit switch L 19 3 4 see page 18 1004...

Страница 16: ...PULL This arm system is delivered with drive arm guide shoe and door fitting It is used if the operator is installed on the wall on the same side as the door swing for example the door is pulled open...

Страница 17: ...1 4 Reveal Spacer PULL 8 1 5 Drive Shaft Extension Kits 8 2 Tool Kit to change rotation direction 40 mm 1 9 16 60 mm 2 3 8 40 1 9 16 60 2 3 8 P N 173804BK 20 mm 3 4 P N 21 03 205 P N 21 03 206 50 mm 2...

Страница 18: ...nsion Unit EXB 8 6 Control Switches 8 6 1 4 Position Switch with Key PS 4C with EXB 8 6 2 3 Position Switch PS 3B P N 100147 P N 655614 L 19 3 4 P N 1004205 L 78 3 4 20 21 22 23 24 25 26 27 28 29 30 3...

Страница 19: ...ual Side Automatic Door Do Not Enter Out P N 75 20 101 Dual Side Automatic Door Do Not Enter In P N 75 20 102 Dual Side Caution Automatic Door P N 1001695 Dual Side Supervision of child P N 21 24 006...

Страница 20: ...8 8 2 Remote Transmitter Push Plates 8 8 3 Installation Box for Narrow Plates 8 8 4 Remote Receiver PUSH TO OPEN P N 75 02 273 PUSH TO OPEN P N 75 02 272 PUSH TO OPEN P N 75 02 269 PUSH TO OPEN P N 7...

Страница 21: ...stallation points Inspect the door hinges before installation to ensure that they are in good repair Unpack the operator and make sure that all parts are delivered in accordance with the packing note...

Страница 22: ...xamples 1 Aluminum profile system 2 Plasterboard wall 3 Reinforced concrete wall and brick wall 4 Plasterboard wall A Steel reinforcement or rivnut B Wood reinforcement C Expansion shell bolt for bric...

Страница 23: ...ne sealant Installation and Service Manual 1004935 US 1 0 this manual 9 6 Installation on double doors If the operators are to be mounted at the same height with pushing and pulling arm systems the he...

Страница 24: ...tems PUSH SAS F which push the door open and PULL which pull the door open See also QuickStart which is enclosed with each operator 10 1 Wall Mounted Operator with Arm System PUSH SAS F 2 3 0 9 16 1 7...

Страница 25: ...MVI Impulse 1003870 ALL TB1 AND TB2 CLASS 2 SUPPLY MAX 24 V 0 V DC 24 V DC Motor control Slave ON 1 2 3 4 5 6 7 8 H O T Opening Delay MVI H O T 5 6 7 8 5 6 7 9 8 10 1 2 3 4 2x 6 C L 1 701500 HSO HSO...

Страница 26: ...26 Issue 2008 11 13 1004935 US 1 0 Cont Wall Mounted Operator with Arm System PUSH SAS F 7 8 9 90 2 3 8 90 19 lbf ft...

Страница 27: ...on 701500 HSO HSO LSO LSO LSC LK HSC HSC LSC 701448 701448 LK 701500 HSO HSO LSO LSO LSC LK HSC HSC LSC 701448 701448 LK 701500 HSO HSO LSO LSO LSC LK HSC HSC LSC 701448 701448 LK 701500 HSO HSO LSO L...

Страница 28: ...3 1004935 US 1 0 10 2 2 Installation of Operator with Arm System PULL 1 2 3 1 13 16 2 5 8 3 3 4 4 9 16 Z _ 1 9 16 x 2 3 8 Z 5 1 8 1 3 8 7 8 C L 2 PULL Right hand 3 4 2 2 3 4 2x C L 1 Z 4 5 16 22 15 16...

Страница 29: ...1004935 US 1 0 Issue 2008 11 13 29 Cont Installation of Operator with Arm System PULL 4 5 8 1 4...

Страница 30: ...30 Issue 2008 11 13 1004935 US 1 0 Cont Installation of Operator with Arm System PULL 19 lbf ft Connects to High Voltage Power Source see page 33...

Страница 31: ...1004935 US 1 0 Issue 2008 11 13 31 Cont Installation of Operator with Arm System PULL...

Страница 32: ...ator can be equipped with different control units adapted to the functions required 11 1 1 CSDB This basic control unit is equipped with inputs for connection of automatic and man ual activation units...

Страница 33: ...DC 24 V DC 1 2 3 4 TB1 FS 120 V AC 60 Hz ON 1 2 3 4 5 6 7 8 max 700 mA 2 0 V DC 0 V DC Kill Key Impulse Lock 24 V DC N C ock Door o power until closing off on e 1003870 or control ntrol T lay H O T 5...

Страница 34: ...B CSDB 8 7 6 5 4 3 2 1 9 10 701500 HSO HSO LSO LSO LSC LK HSC HSC LSC 701448 LK N L TB2 701500 HSO HSO LSO LSO LSC LSC LK LK HSC HSC HSC HSC LSC LSC 701448 701448 LK LK Slave Master 2 0 V DC 0 V DC Ki...

Страница 35: ...C NO 0 V DC 0 V DC OFF EXIT 24 V DC 0 V DC OPD MAT Lock out 24 V DC 0 V DC 24 V DC 20 21 22 23 TB3 24 25 26 27 28 29 TB4 30 31 32 33 34 35 36 TB5 37 Note It is important that the high and low voltage...

Страница 36: ...ctory Note If the installation requires adjustment of the closing torque follow the instructions on page 37 4 Adjust the opening angle by using the limit switch The limit switch is slid into a groove...

Страница 37: ...xtremely low torque is adjusted 12 2 Opening torque If the closing torque spring force has been changed or if the door does not open to its full extent the opening torque pump pressure must be adjuste...

Страница 38: ...25 20 20 21 21 EXB TB3 EXB TB4 EXB TB3 32 30 31 26 21 22 23 24 EYE TECH Bodyguard 4 SAFE 7 8 1211 8 CSDB TB2 CSDB TB2 CSDB TB2 6 24 V AC DC 7 11 13 13 7 14 1211 14 PS 2 1 3 3 2 CSDB TB2 7 8 1 3 2 11 1...

Страница 39: ...end plates for cover 3 Earth Fastening screw 2 Bottom end plate 4 Besam logotype X 1 L C 1 9 16 ILL 02016 The cover is slid over flanges in the back plate so that the ridges fit in the grooves Secure...

Страница 40: ...door standard for one way and two way traffic applications 50 12 50 12 34 48 50 12 58 5 C L Apply to both sides of the door When using a wall switch apply to both sides of the door Apply the push dec...

Страница 41: ...t close Constant impulse is created Disconnect activation unit or replace control unit The door does not open fast enough Pump pressure is too low Adjust pump pressure The door delays before opening L...

Страница 42: ...maintenance to have a reliable and safe product Service and adjustments will ensure a safe and proper operation of an automatic door unit The table below shows the recommended interval in months when...

Страница 43: ...1004935 US 1 0 Issue 2008 11 13 43...

Страница 44: ...nd convenience ASSA ABLOY is the global leader in door opening solutions dedicated to satisfying end user needs for security safety and convenience Besam US Inc 1900 Airport Road US Monroe NC 28110 Te...