AL-500 Series
Installation Instructions
Alarmed Exit Devices
1-800-327-8539 • www.arrowlock.com
Copyright © 2019, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved.
Reproduction in whole or in partwithout the express written permission of ASSA ABLOY Access and
Egress Hardware Group, Inc. is prohibited.
1
General Description
The Alarmed Exit is designed for areas that require an alarm to sound upon exiting. Once armed, any push
rail movement will activate the horn in the push rail. The horn will continue to sound for two (2) minutes
and shut off automatically. The LED will flash, indicating a violation has occurred.
Alarmed Exit
Circuitry
Figure 1
Manual dogging is provided standard
on non fire rated devices
2
Miscellaneous Parts
Endcap
Mounting Plate
Exit Rail
Exit device
chassis and rail
assembly shown
Chassis
Assembly
Cover
Mounting rail insert
Figure 2
3
Dip Switch (SW-2, 6-position)
Factory settings shown.
1. DS-1 = OFF, DS-2 = OFF - REX / Passage Delay (set to 7 seconds).
2. DS-3 = OFF, DS-4 = OFF - Automatic Alarm Reset (set to 2 minutes).
3. DS-5 = ON - Selects LED color (Armed = Green, Violation = Red, Passage = Yellow).
4. DS-6 = ON - Monitor Relay is enabled (will activate when rail is violated).