Document No: ST-001323-C, Issue date: 21 February 2014

Содержание Aperio AH15

Страница 1: ...The global leader in door opening solutions Aperio Online Mechanical Installation Manual Document No ST 001323 C Issue date 21 February 2014 ...

Страница 2: ...ence 6 4 Mechanical Installation 7 Mechanical installation AH15 7 Installation examples for AH15 communication hub with E cylinder locks 9 Installation examples for AH15 communication hub with other type of locks 14 Mechanical installation AH20 30 40 17 Installation examples for AH20 30 40 communication hub 19 5 Configuration and Connection of Cables 25 AH15 RS 485 25 AH15 Wiegand 28 AH20 Wiegand ...

Страница 3: ...ual software for setup of Aperio products for final use with an EAC Applicable Products This manual can be used for all versions of communication hubs Product availability The products included in this manual may not be available on all markets Please check your local ASSA ABLOY company for details Aperio support in the EAC system Note that the Aperio support may vary depending on the Aperio commu...

Страница 4: ...Aperio USB radio device connected to one of its USB ports The USB radio device enables the application to connect via a Communication Hub to the door lock The lock communicates via the Communication Hub either with the EAC or with the Programming Application Read more in the Aperio Online Programming Application Manual Regulatory and security information Refer to the Programming Application manual...

Страница 5: ...antenna is used the radio coverage backwards is limited to 0 5 m 3 ft for AH15 and 3 m 10 ft for AH20 30 40 The coverage also depends on the type of wall it is installed on When the external antenna is used the radio coverage will be focused perpendicular to the direction of the antenna and in some directions the range may decrease However the maximum range will not increase See section Radio cove...

Страница 6: ...Fi WLAN routers and other radio transmitters operating in the 2 4 GHz band should be kept at least 3 5 meters 12 feet from the Communication Hub and lock Other possible sources of interference include microwave ovens electric motors wireless emergency exit signs and other high power electrical equipment Keep at least 3 5 meters 12 feet distance to Communication Hub or lock In difficult environment...

Страница 7: ...ine EAC system This chapter also describes how to connect the communication hubs to the power supply Mechanical installation AH15 Minimum distance between AH15 communica tion hubs If necessary several communications hubs can be positioned together with a minimum of 0 2 meter in between the hubs or use one AH30 communication hub to pair with all three locks X X 0 2 m 8 in X Figure 3 Minimum distanc...

Страница 8: ...rallel to the direction of the lock and as close to the lock as possible The following pages show typical installations based on field experience that will give a good result for radio link quality The colors indicate which hubs and Aperio door locks that belong together 4 m 13 ft Parallel 5 m 16 ft The AH15 communication hub can be mounted according to the following figure AH15 Communication hub ...

Страница 9: ...nical Installation Guide Document No ST 001323 B Date 21 februari 2014 9 Aperio Online Installation examples for AH15 communication hub with E cylinder locks Short long Corridors Alternate installation 5 m 16 ft 5 m 16 ft ...

Страница 10: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 10 High ceiling 5 m 16 ft 5 m 16 ft 4 m 13 ft Low ceiling 5 m 16 ft 5 m 16 ft 1 5 4 m 5 13 ft ...

Страница 11: ...e Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 11 Aperio Online Square rooms 5 m 16 ft 5 m 16 ft Alternate installation with ceiling placement 5 m 16 ft 5 m 16 ft 5 m 16 ft 5 m 16 ft ...

Страница 12: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 12 Open space environments 5 m 16 ft 5 m 16 ft 5 m 16 ft 5 m 16 ft ...

Страница 13: ...nting holes vertically aligned and as close to the lock as possible The following pages show typical installations based on field experience that will give a good re sult for radio link quality The colors indicate which hubs and Aperio door locks that belong together The AH15 communication hub can be mounted according to the following figure AH15 Communication hub installed on a wall with mounting...

Страница 14: ...ation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 14 Installation examples for AH15 communication hub with other type of locks Corridors 4 m 13 ft 5 m 16 ft Alternate installation on same wall 4 m 13 ft 5 m 16 ft ...

Страница 15: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 15 Aperio Online Square rooms 5 m 16 ft 5 m 16 ft Alternate installation on same wall 5 m 16 ft 5 m 16 ft ...

Страница 16: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 16 Open space environments 5 m 16 ft 5 m 16 ft ...

Страница 17: ... under good conditions free air between the units and limited radio interference from other transmitters the distance can be extended The following pages show typical installations based on field experience that will give a good re sult for radio link quality The colors indicate which hubs and Aperio door locks that belong together The AH20 30 40 communication hub can be mounted according to the f...

Страница 18: ... does not extend the maximum range which is still 15 m 50 ft An example of a situation where external antenna could be used is when the placement options are limited for the communication hub The following figure illustrates the difference in radio pattern for external and internal antenna Note that this is only an simplified picture of the radio reception for each antenna showing the theoretical ...

Страница 19: ...ine Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 19 Aperio Online Installation examples for AH20 30 40 communication hub Short Corridors 15 m 50 ft Alternate installation 15 m 50 ft ...

Страница 20: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 20 Long corridors 30 m 100 ft Alternate installation 30 m 100 ft ...

Страница 21: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 21 Aperio Online High ceiling 15 m 50 ft 5 m 16 ft Alternate installation 15 m 50 ft 5 15 m 16 50 ft ...

Страница 22: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 22 Low ceiling 15 m 50 ft 1 5 5 m 5 16 ft ...

Страница 23: ...o Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 23 Aperio Online Square rooms 15 m 50 ft 15 m 50 ft Alternate installation with light wall material 15 m 50 ft 20 m 50 ft ...

Страница 24: ...Aperio Online Mechanical Installation Guide Document No ST 001323 B Date 21 februari 2014 Aperio Online 24 Open space environments 15 m 50 ft 15 m 50 ft Alternate installation 15 m 50 ft 15 m 50 ft ...

Страница 25: ...tomatic paring mode or manual selection of EAC address on the RS485 Default configuration is to select an address according to below By doing so automatic pairing will be deactivated DIP 1 5 Pairing mode If DIP 1 5 are set to OFF pairing mode will be activated This means that after powering on the communication hub it will automatically try to pair with locks within range Automatic pairing will on...

Страница 26: ...ition for all communication hubs except for the communication hub at the end of the bus which must have DIP switch 8 in ON position The RS 485 bus must be terminated on the EAC side EAC system A B A Termination enabled B A B A B Hub 1 DIP 6 OFF DIP 7 OFF DIP 8 OFF Hub 2 DIP 6 OFF DIP 7 OFF DIP 8 OFF Hub N End of Bus DIP 6 ON DIP 7 ON DIP 8 ON For a star connection set DIP 6 and 7 in ON position fo...

Страница 27: ...n the EAC system a maximum of 32 units 31 communication hubs plus the EAC when using the DIP Switch for RS 485 addressing can be connected to the same bus Connect all RS485 A connectors together and all RS485 B connectors together depending on connection type see Figure 8 and Figure 9 on page 26 Connecting to supply voltage Connect the wires to 8 24 VDC 0 9 W and GND ground on the communication hu...

Страница 28: ...ce component 3 A2 Controls addition of parity bits on transmitted credentials One even parity bit before and one odd parity bit after the actual credentials OFF Addition of parity is disabled Credentials are transmitted as received ON Addition of parity bits is enabled 2 A1 Reserved for future use Set to OFF 1 A0 Controls use of Red LED signal for access decision ON Red LED is used OFF Red LED is ...

Страница 29: ...ired Yes Yes Figure 10 Dip Switch 1 OFF Access decision logic with single LED signal Red LED active Data from RFID reader Transmit via Wiegand interface On completion start timer 1 5 s Signal access denied to lock Signal access granted to lock No No No No No Yes Yes Green LED active Red LED active Timer expired Exit without access decision to lock This means that override credentials will be used ...

Страница 30: ...t to OFF DIP 3 Parity bit Note Transmitted credentials may include parity anyway although addition of parity is disabled in the Hub Wiegand EAC interface component The reason is that parity bits are usually already included on the credential DIP 4 Byte Order Note This setting is ignored if the credential length does not make up complete bytes Note The byte order received as input to the Hub Wiegan...

Страница 31: ...onnect to a lock control relay output on EAC system RED Wiegand Red LED signal Input to communication hub Used for access decision Wiegand Red LED output on EAC system Alternatively leave unconnected if signal is selected not to be used by DIP switch 1 DATA0 Wiegand Data 0 signal Output from communication hub Used to transmit credentials Wiegand Data 0 on EAC system DATA1 Wiegand Data 1 signal Out...

Страница 32: ...d as input to the Hub Wiegand EAC interface component 3 A2 Controls addition of parity bits on transmitted credentials One even parity bit before and one odd parity bit after the actual credentials OFF Addition of parity is disabled Credentials are transmitted as received ON Addition of parity bits is enabled 2 A1 Set to OFF Reserved for future use 1 A0 Controls use of Red LED signal for access de...

Страница 33: ...ired Yes Yes Figure 13 Dip Switch 1 OFF Access decision logic with single LED signal Red LED active Data from RFID reader Transmit via Wiegand interface On completion start timer 1 5 s Signal access denied to lock Signal access granted to lock No No No No No Yes Yes Green LED active Red LED active Timer expired Exit without access decision to lock This means that override credentials will be used ...

Страница 34: ...on time out in this case DIP 2 Future use Note This DIP must always be set to OFF DIP 3 Parity bit Note Transmitted credentials may include parity anyway although addition of parity is disabled in the Hub Wiegand EAC interface component The reason is that parity bits are usually already included on the credential DIP 4 Byte Order Note This setting is ignored if the credential length does not make ...

Страница 35: ...APPLICABLE DATA1 Wiegand Data 1 signal Output from communication hub Used to transmit credentials Wiegand Data 1 on EAC system DATA0 Wiegand Data 0 signal Output from communication hub Used to transmit credentials Wiegand Data 0 on EAC system RED Wiegand Red LED signal Input to communication hub Used for access decision Wiegand Red LED output on EAC system Alternatively leave unconnected if signal...

Страница 36: ... 4 5 6 7 8 9 10 ON S101 J100 J103 S100 Relays Description Relay 1 K500 DPS Door Position Sensor Relay 2 K501 RX Request to exit Relay 3 K502 Battery Alarm Output Relay 4 K503 Tamper Alarm Output Lock Jammed Relay Contacts Description NCL Normal Closed COM Common NOP Normal Open Relay max voltage 30 VDC Relay max current 1 A resistive load Connecting to supply voltage Connect the wires to 8 24 VDC ...

Страница 37: ... 3 A2 Manual EAC Address 2 A1 Manual EAC Address 1 A0 Manual EAC Address Automatic pairing DIP 1 5 OFF DIP 1 5 Selecting the EAC address Automatic paring The DIP 1 5 has two functions either automatic paring mode or manual selection of EAC address on the RS485 Default configuration is to select an address according to below By doing so automatic pairing will be deactivated DIP 1 5 Pairing mode If ...

Страница 38: ...x17 0x27 0x37 0x47 0x57 0x67 0x77 1000 0x08 0x08 0x18 0x28 0x38 0x48 0x58 0x68 0x78 1001 0x09 0x09 0x19 0x29 0x39 0x49 0x59 0x69 0x79 1010 0x0A 0x0A 0x1A 0x2A 0x3A 0x4A 0x5A 0x6A 0x7A 1011 0x0B 0x0B 0x1B 0x2B 0x3B 0x4B 0x5B 0x6B 0x7B 1100 0x0C 0x0C 0x1C 0x2C 0x3C 0x4C 0x5C 0x6C 0x7C 1101 0x0D 0x0D 0x1D 0x2D 0x3D 0x4D 0x5D 0x6D 0x7D 1110 0x0E 0x0E 0x1E 0x2E 0x3E 0x4E 0x5E 0x6E 0x7E 1111 0x0F 0x0F 0...

Страница 39: ...ll communication hubs except for the communication hub at the end of the bus which must have DIP switches 6 8 in ON position The RS 485 bus must be terminated on the EAC side EAC system A B A Termination enabled B A B A B Hub 1 DIP 6 OFF DIP 7 OFF DIP 8 OFF Hub 2 DIP 6 OFF DIP 7 OFF DIP 8 OFF Hub N End of Bus DIP 6 ON DIP 7 ON DIP 8 ON For a star connection set DIP 6 and 7 in ON position for one c...

Страница 40: ... 485 bus should be made up of a twisted pair cable with characteristic impedance between 90 Ohm and 120 Ohm Maximum bus length is about 1000 m Depending on the EAC system a maximum of 32 units 31 communication hubs plus the EAC when using the DIP Switch for RS 485 addressing can be connected to the same bus Connect all RS485 A connectors together and all RS485 B connectors together depending on co...

Страница 41: ... activate automatic pairing connect the two left pins PAIR with the jumper see figure Connect to supply voltage Connect the power and ground to the and the terminals of the connector marked 8V 24V Note Power supply input 8 24 VDC 3 5 W The power supply shall be a Limited Power Source LPS according to EN 60950 1 The power supply shall be 3 A over current protected Wire requirements 16 22 AWG Connec...

Страница 42: ... can pair with up to 8 locks When pairing several locks to a communication hub the following addresses are used for the address range 1 15 Above this range only one lock can be paired DIP 4 DIP 1 AH30 Hub address Lock addresses 0000 Reserved 0001 0x01 0x01 0x11 0x21 0x31 0x41 0x51 0x61 0x71 0010 0x02 0x02 0x12 0x22 0x32 0x42 0x52 0x62 0x72 0011 0x03 0x03 0x13 0x23 0x33 0x43 0x53 0x63 0x73 0100 0x0...

Страница 43: ... this mode are set consecutively For example if communication hub has address 1 the locks will get address 1 8 9 16 17 24 etc DIP 5 DIP 1 AH30 Hub address Lock addresses 0000 Reserved 0001 0x01 0x01 0x02 0x03 0x04 0x05 0x06 0x07 0x08 0010 0x02 0x09 0x0A 0x0B 0x0C 0x0D 0x0E 0x0F 0x10 0011 0x03 0x11 0x12 0x13 0x14 0x14 0x16 0x17 0x18 0100 0x04 0x19 0x1A 0x1B 0x1C 0x1D 0x1E 0x1F 0x20 This mode is use...

Страница 44: ...e of installation since all the lock addresses used are unique Addressing is simply made by selecting a unique address for each communication hub Mixed installation A mixed installation uses both AH15 and AH30 communication hubs with the address range from 1 to 63 according to this figure Lock 0x01 Lock 0x11 Lock 0x21 Lock 0x02 Lock 0x03 Lock 0x13 Lock 0x11 Lock 0x2F AH30 0x01 AH15 0x02 AH30 0x03 ...

Страница 45: ... paired If so use the Programming Application to unpair any locks Upgrading firmware in AH30 communication hubs The latest firmware 2 6 0 or later for AH30 communication hubs adds the functionality to use DIP Switch addresses in the range of 16 31 DIP switch 5 Before upgrading make sure that your existing AH30 communication hubs do not have DIP 5 activated If DIP 5 is activated and the communicati...

Страница 46: ...en three red flashes Aperio lock and EAC offline Yellow off fast flash UHF communication Some special LED indication schemes are used during lock maintenance actions Yellow green flashes Pairing active 2 sec AH40 Ethernet LED indication The LED on the AH40 communication hub indicates both the status of the Ethernet link level and ethernet communication 2 sec Green Green off fast flash Ethernet lin...

Страница 47: ... Three red flashes 5 second each Lock mechanism is blocked when closing Tamper Ten red flashes 125 sec each Repeated every 10 sec Time to replace the battery Error in lock maintenance required Ten red flashes 125 sec each Repeated every 10 sec if lock cannot close 2 1 Battery reached end of life lock disabled Card access configurable Card PIN access configurable EAC response time Enter PIN One yel...