2.3.  Dimensions of the product

Look and dimensions of the module are shown below. The module is mounted

directly to the rail in the DIN industry standard. Power connectors, communication and
IOs   are   at   the   bottom   and   top   of   the   module.   USB   connector   configuration   and
indicators located on the front of the module.

3.  Communication configuration

3.1.  Grounding and shielding

In most cases, IO modules will be installed in an enclosure along with other

devices which generate electromagnetic radiation. Examples of these devices are relays
and contactors, transformers, motor controllers etc. This electromagnetic radiation can
induce electrical noise into both power and signal lines, as well as direct radiation into
the module causing negative effects on the system. Appropriate grounding, shielding
and other protective steps should be taken at the installation stage to prevent these
effects. These protective steps include control cabinet grounding, module grounding,
cable   shield   grounding,   protective   elements   for   electromagnetic   switching   devices,
correct wiring as well as consideration of cable types and their cross sections.

3.2.  Network Termination

Transmission   line   effects   often   present   a   problem   on   data   communication

networks. These problems include reflections and signal attenuation.

To eliminate the presence of reflections from the end of the cable, the cable must

be terminated at both ends with a resistor across the line equal to its characteristic
impedance.  Both   ends  must  be  terminated  since   the  direction   of  propagation  is  bi-
directional. In the case of an RS485 twisted pair cable this termination is typically
120 Ω.

Expansion Module – 1 temperature input, 1 digital output

© 

SfAR

 2011 - 2014. All rights reserved.

User Manual

Version 1.0 - 02/01/2014

5 / 12

90

17

56

50

34

Содержание Sfar Mini Modbus 1TE

Страница 1: ...Mini Modbus 1TE Expansion Module 1 temperature input 1 digital output Version 1 0 02 01 2014 User Manual Manufactured for...

Страница 2: ...the purposes of commercial law This information does not release you from the obligation of own judgment and verification We reserve the right to change product specifications without notice Please r...

Страница 3: ...n addition the module has one configurable digital outputs PNP or NPN Values are read via RS485 Modbus so we can easily integrate the module with popular PLCs HMI or PC equipped with the appropriate a...

Страница 4: ...1700 C B thermocouple operation range 0 C 1800 C Resistance From 0 to 8000 1 resolution Voltage 0 to 2048mV 0 1mV resolution 0 to 256mV 0 01mV resolution Resistance measuring current 250 A Measurement...

Страница 5: ...te grounding shielding and other protective steps should be taken at the installation stage to prevent these effects These protective steps include control cabinet grounding module grounding cable shi...

Страница 6: ...gistered Read 3 4 40001 Output Registers Registered Read Write 4 6 16 3 4 Communication settings The data stored in the modules memory are in 16 bit registers Access to registers is via MODBUS RTU or...

Страница 7: ...3 0x03 Data Bits MSB 7 7 data bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII 4 Indicators Indicator Description ON LED indicates that the module is c...

Страница 8: ...IN DO USB PT100 2 wire measurement V V SUPPLY 10 36V COM INB INA OUT V GND 485 485 VCC GND Mini Modbus 1TE SfAR ON TX IN DO USB Thermocouple measurement V V SUPPLY 10 36V COM INV INA OUT V GND 485 48...

Страница 9: ...rite 30051 50 0x32 Inputs Read Connected sensors Bit in high state sensor is connected 40052 51 0x33 Outputs Read Write Alarms state bit 2 alarm output 30053 52 0x34 Temperature Read Temperature or me...

Страница 10: ...utput is set if value is greater than Alarm Value register 40065 cooling 512 Output is set if value is less than Alarm Value register 40065 heating 40063 62 0x3E Alarm Value Read Write Alarm value for...

Страница 11: ...s of the module This program can be a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is done via the USB cable The module does...

Страница 12: ...gisters 6 3 4 Communication settings 6 3 4 1 Default settings 6 3 4 2 Configuration registers 7 4 Indicators 7 5 Block diagram 8 6 Module Connection 8 7 Modules Registers 9 7 1 Registered access 9 7 2...

Отзывы: