SfAR
Mini Modbus 1TE
User Manual
40061
60
0x3C Input settings
Read & Write
Analog input mode:
0 – input disabled
1 – voltage to 2048mV
2 – voltage to 256mV
3 – J thermocouple
4 – K thermocouple
5 – T thermocouple
6 – N thermocouple
7 – S thermocouple
8 – R thermocouple
9 – B thermocouple
10 – Pt100 3-wire
11 – Pt100 2-wire
12 – resistance to 8kΩ
13 - Ni100
14 – KTY81-110
15 – Pt500 3-wire
16 – Pt500 2-wire
17 – Pt1000 3-wire
18 – Pt1000 2-wire
19 – NTC Carel 2-wire
+32 – junction temperature is taken from register
40081 "Constant junction temperature"
40062
61
0x3D Output settings
Read & Write
Alarm output settings
0 – output is set by PLC
+256 – Output is set if value is greater than Alarm
Value (register 40065) („cooling”)
+512 – Output is set if value is less than Alarm Value
( register 40065) („heating”)
40063
62
0x3E Alarm Value
Read & Write
Alarm value for outputs
40064
63
0x3F Alarm hysteresis
Read & Write
The hysteresis value for alarm outputs
40065
64
0x40 Input resistance
Read & Write
Lead wire resistance for each input
7.2. Bit access
Modbus
Address
Dec
Address
Hex
Address
Register
name
Access
Description
801
800
0x320 Input
Read
Set when the sensor is connected
817
816
0x330 Alarm
Read
Alarm state
818
817
0x331 Digital output
Read & Write
State of digital output
1
Sensor must be connected in paraller to resistor 7.5kΩ 1%
Expansion Module – 1 temperature input, 1 digital output
©
SfAR
2011 - 2014. All rights reserved.
User Manual
Version 1.0 - 02/01/2014
10 / 12