RS485 MODBUS Module 16O
User Manual
8. Modules Registers
8.1. Registered access
Modbus Dec Hex
Register Name
Access
Description
30001
0
0x00 Version/Type
Read
Version and Type of the device
30002
1
0x01 Switches
Read
Switches state
40003
2
0x02 Baud rate
Read & Write
RS485 baud rate
40004
3
0x03 Stop Bits & Data Bits
Read & Write
No of Stop bits & Data Bits (see 3.5.3)
40005
4
0x04 Parity
Read & Write
Parity bit
40006
5
0x05 Response Delay
Read & Write
Response delay in ms
40007
6
0x06 Modbus Mode
Read & Write
Modbus Mode (ASCII or RTU)
40009
8
0x08 Watchdog
Read & Write
Watchdog
40013
12 0x0C Default Output State
Read & Write
Default output state (after power on or
watchdog reset)
40033
32 0x20 Received packets LSB Read & Write
No of received packets
40034
33 0x21 Received packets MSB Read & Write
40035
34 0x22 Incorrect packets LSB
Read & Write
No of received packets with error
40036
35 0x23 Incorrect packets MSB Read & Write
40037
36 0x24 Sent packets LSB
Read & Write
No of sent packets
40038
37 0x25 Sent packets MSB
Read & Write
40052
51 0x33 Outputs
Read & Write
Output state
Expansion Module– 16 digital outputs
User Manual
Version 1.2
13 / 16