RRM02 - Product Manual
Issue: 02 complete, approved
Page 36 of 68
6
Commissioning the RRM02
6.1
For a Single RRM02 Unit with Serial Data and Audio Connection
to an ASL Router Audio Input
For operational details refer to your system specific documentation; see
Table 10
(page
64
).
L
The following details are correct for the current VAR Router, DAU, and ACU software versions
at the time of publication:
•
VAR4/12/20 Router: CP 4.1.471
•
Intellevac DAU/VAR8: CP V1.6.124
•
Intellevac ACU/VAR8-ACU: CP V1.5.115
If any difficulties are encountered, then refer to Application Solutions (Safety and Security)
Limited for advice quoting the software version of your system. The software version is
displayed via the
Configuration
→
System
→
Misc
→
Software
menu.
Configure the RRM02 from the Router Configuration Tool, or system front panel as described in the following
sections.
6.1.1
Obtaining the Router Input Number
Check the system design documentation to find the Router audio input number being used for the RRM02.
This input number will be required throughout this commissioning procedure, being referred as
nn
.
6.1.2
Configuring the Microphone Type
Menu:
Configuration
Æ
System
Æ
Router
Æ
Inputs
Æ
Mic/Line
Æ
<I/P #
nn
–
input name
>
Where
nn
is the Router input number found in Section “
6.1.1 Obtaining the Router Input Number
”
(page
36
).
Configure the RRM02 as
Single Button Microphone
.
6.1.3
Configuring the PTT Button
6.1.3.1
PTT Button Zone Selection
Menu:
Configuration
Æ
System
Æ
Router
Æ
Inputs
Æ
Mic/Line
Æ
<I/P #
nn
–
input name
>
Æ
Single Button Microphone
Æ
PTT
Æ
PTT Zones
Possible values:
‘Not-Selected’ or ‘Selected’
System default configuration: ‘Not-Selected’
Select the output or group of outputs to which the microphone is to be routed when the PTT button is
pressed.
Consult the system design documentation for which outputs are used for which audio zones. Note that to
simplify this process the Router may have had the output names changed to zone names in the
Configuration
Æ
System
Æ
Router
Æ
Outputs
menu.