Ashley EC95 Скачать руководство пользователя страница 19

EC95

19

INSTRUCTION MANUAL ADDENDUM

This addendum is a supplement to the Installation, Operation, and Maintenance Instruction Manual for this appliance.  Do
not neglect to read all instructions thoroughly.

ATTENTION:  Installers of Fireplaces, Fireplace Stoves, Room Heaters, and Fireplace Inserts.

SUBJECT:  Determining Equivalent Materials for Use as Hearth Extensions and Floor Protectors Over Combustible

      Floors.

1.  If you are not a qualified installer of the product, we suggest that you consult with a qualified installer or other knowledge-
able person for proper installation of the product. Your local building code official should also be consulted.

2.  Refer to the section in the installation instructions on hearth extensions or floor protectors.  Use the material specified
in the instructions.

3.  If a listed floor protector is specified as an alternate material, consult a local dealer that sells floor protectors which are
listed by a recognized listing agency.  If the solid fuel burning appliance requires one or two layers of 3/8 inch thick
millboard, a Listed floor protector may be purchased that is intended for use in place of the required number of layers of
millboard as specified in the instructions.

4.  If an equivalent material for use as a hearth extension or floor protector is permitted in the installation instructions and
a K, C, or R factor is specified, be sure (a) that the equivalent material is Listed by a recognized listing agency, (b) that the
K or C factor is equal to or less than the number specified and (c) the thickness of the material is at least equal to the
specified thickness in the installation instructions.  The K factor for millboard is equal to 0.84 BTU-inch/(hr.) (°F) (ft

2

), which

can be used to determine equivalency under Item 3 if necessary.

5.  For reference, K, C, and R factors are given for building and insulating materials in engineering handbooks such as the
ASHRAE Handbook of Fundamentals and the Standard Handbook for Mechanical Engineers by Baumeister and Marks.

6.  K, C, and R factors are explained as follows:

A.  The “K” factor represents the thermal conductivity of a material and is the time rate of heat flow through a
homogeneous material under steady-state conditions, through unit area, per unit temperature gradient in the
direction perpendicular to a surface.      BTU

or

(Btu)(in.)

_______________

________________________

(hr)(ft

2

)(°F/in.)

(hr)(ft

2

)(°F)

B.  The “C” factor represents the thermal conductance of a material at a specific thickness and is applied to a
specific homogenous material used at the stated thicknesses.  (Note: The “C” factor is equal to the “K” factor
divided by the thickness of material.)
C.  The “R” factor represents the thermal resistance of a material and is defined as the reciprocal of either the
“K” or “C” factor, expressed as “R per inch” (K factor reciprocal) or “R” with reference to a specific material
thickness related to a specific application (C factor reciprocal).

REFERENCES:

1.  ASHRAE Handbook, 1981 Fundamentals, published by American Society of Heating, Refrigerating and Air-Conditioning
Engineers, 1981; Chapter 23.

2.  Eshbach, O. W., Handbook of Engineering Fundamentals, published by Wiley & Sons, 1936, 1952; Table 2, pp. 13-39
to 13-43.

Note:  Use of the K and C constants needs to be carefully considered since the exact number depends on the system of
units involved.  The value of the constant is different under different systems of units.  K is identified in some tables as “per
inch”; however, from a unit consideration, the “inch” (i.e. thickness) is actually in the numerator, not the denominator, and
to determine the K factor for a specific thickness (i.e., the C factor), it is necessary to divide by the thickness of the
material.  Other handbooks or manufacturers’ data cancel the inch of thickness in the numerator with the square feet of
area in the denominator of the K factor, resulting in a variance of 12 in the table of values or in the manufactors’ data.  An
example calculation is as follows:
If the floor protector or hearth extension material is specified as one layer of 3/8 inch (0.375 inch) thick millboard with a K
factor of 0.84, the following calculations apply:

Содержание EC95

Страница 1: ...ULT FOR YOUR SAFETY FOLLOW THE INSTALLATION INSTRUCTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRIC TIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA To assure that satisfactory...

Страница 2: ...chance of drafts blowing smoke ashes or sparks out of the heater during refueling or ash removal 7 The heater should be located where a small supply of wood may be kept conveniently close but not wit...

Страница 3: ...EC95 3 FIGURE 3 MINIMUM CLEARANCES TO COMBUSTIBLES FIGURE 4 MINIMUM CLEARANCES TO COMBUSTIBLES SIDE SECTION VIEW PLAN SECTION VIEW...

Страница 4: ...btained from N F P A Inc Batterymarch Park Quincy MA 02269 The Chimney connector pipe from heater to chimney must be 6 inches in diameter and made from 24 gauge or heavier steel The length of the chim...

Страница 5: ...el supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section Fasteners used to secure chimney sections shall not penetrate chimney flue l...

Страница 6: ...RICK ALL AROUND CHIMNEY CONNECTOR TO HEATER FIRE CLAY LINER 5 8 MIN WALL THICKNESS MIN 3 1 2 THICK BRICK MASONRY WALL MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 MINIMUM 12 IN TO COMBUSTIBLES PART A FIGUR...

Страница 7: ...RY CHIMNEY CONSTRUCTED TO NFPA 211 SHEET STEEL SUPPORTS 24 GAUGE MIN THICKNESS CHIMNEY CONNECTOR TO HEATER MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN MINIMUM...

Страница 8: ...O APPLIANCES OR HEATERS ARE CONNECTED TO THE SAME FLUE CAUTION THE HEATER MUST BE PLACED ON A LISTED FLOOR PROTECTOR AS NOTED IN THIS MANUAL IF THE FLOOR IS WOOD OR OTHER COMBUSTIBLE FLOORING IF CARPE...

Страница 9: ...obtain the fireplace items called for by figure 4 3 If the heater is to be installed on a combustible floor purchase a listed noncombustible floor protector as described in this manual and install it...

Страница 10: ...UILD A FIRE 1 Set the heater s thermostat control knob to the Hi position See figure 9 2 Open the feed door see figure 10 and lay paper and kindling on the rate in sufficient quantities to ensure good...

Страница 11: ...driven off and shortens the length of time the dense smoke is likely to deposit creosote on the chimney walls 5 DO NOT TAMPER WITH THE INTERNAL THERMOSTAT MECHANISM The thermostat has been designed a...

Страница 12: ...or several days when embedded in ashes VENTING SYSTEM CHIMNEY CONNECTOR AND CHIMNEY The venting system consists of the heater s chimney connector the pipe which connects the heater to the chimney and...

Страница 13: ...at has grown tall can affect the draft of a chimney that was previously trouble free and other factors The common unit used to measure draft is INCHES IF WATER To determine the draft of your chimney a...

Страница 14: ...ns as cleanly as possible Thus you should adjust the amount of wood you put in the heater to the outdoor temperature Placing excessive wood in the heater will cause excessive creosote formation in the...

Страница 15: ...omposition fire starters specifically designed for starting a fire The use of liquid fire starters can cause an explosion within the heater 14 Do use only a Listed High Temperature Type HT Factory bui...

Страница 16: ...t 11 Don t install this heater in a chimney flue that is used by another appliance 12 Don t neglect to clean and inspect your chimney regularly 13 Don t operate this heater with the doors open 14 Don...

Страница 17: ...EC95 17 FIGURE 12 ILLUSTRATION OF REPAIR PARTS SEE LEDGER ON NEXT PAGE FOR PART NAMES AND PART NUMBERS 47 58...

Страница 18: ...Ash Door 1 88057 18 Feed Door Assy 1 69229 19 Latch 1 25048 20 Liner Front 1 40412 22 Shield Door Ptd 1 24870 23 Pan Ash Welded 1 69206 24 Grate 2 40394 25 Angle Grate Support Assy 2 69205 26 Leveler...

Страница 19: ...k for Mechanical Engineers by Baumeister and Marks 6 K C and R factors are explained as follows A The K factor represents the thermal conductivity of a material and is the time rate of heat flow throu...

Страница 20: ...20 EC95...

Отзывы: