6
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during
installation of the stove. Refer to the tables below.
•
Floor to ceiling height must be at least 7’ (2.13m) in all cases.
•
Do not place any combustible material within 4’ (1.2m) of the front of the unit.
• The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue
pipe.
•
The chimney connector must not pass through an attic or roof space, closet or similar concealed
space, a floor, or a ceiling.
•
For Canadian installations, where passage through a wall, or partition of combustible construction is
desired, the installation must conform to CAN/CSA-B365.
• A flue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
• To reduce flue clearances from combustible materials, contact your local safety department.
•
The provision that clearances may only be reduced by means approved by regulatory authority
4 3/4
(121mm)
54
(1.37M)
*16
(407mm)
18
(458mm)
51
(1296mm)
84
(2134mm)
23.25”
(989mm)
12
(305mm)
18
(458mm)
*14
(356mm)
12
(305mm)
36
(914mm)
INCHES (METRIC)
NOTE: DASHED LINES SHOW
STRAIGHTUP AND DOWN THROUGH
THE WALL INSTALLATION.
*CANADIAN INSTALLATIONS REQUIRE
A MINIMUM OF 18” (450mm) ON THE
FUEL LOADING SIDE AND 8”(203mm)
ON ALL OTHER SIDES.
NON-COMBUSTIBLE CONSTRUCTION
IN ACCORDANCE WITH NFPA 211
AND CAN/CSA-B365-M91
18”
(458mm)
12”
(304.8mm)
18”
(458mm)