-4-
INSTALLATION
POSITIONING THE STOVE
It is very important to position the stove as close as possible to the chimney, and in an area that will favor the
most efficient heat distribution possible throughout the house. The stove must therefore be installed in the room
where the most time is spent, and in the most spacious room possible. Recall that stoves produce radiating
heat, the heat we feel when we are close to a stove. A stove also functions by convection, that is through
the displacement of hot air accelerated upwards and its replacement with cooler air. If necessary, the hot air
distribution from the stove may be facilitated by the use of a fan or blower.
FREE STANDING STOVE INSTALLATION
A stove must never be installed in a hallway or near a staircase, since it may block the way in case of fire or fail
to respect required clearances. It is of the utmost importance that the clearances to combustible materials be
strictly adhered to during installation of the stove. Refer to the table and diagrams below for minimum required
clearances.
•
Do not place any combustible material within 4’ (1.2m) of the front of the unit.
• The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
•
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
floor, or a ceiling.
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back w
all / A
rr
ièr
e M
ur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M
M
C
B
A
E
E
D
D
F
G
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back w
all / A
rr
ièr
e M
ur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M
M
C
B
A
E
E
D
D
F
G
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back wall / Arrière Mur
Side w
all / P
ar
oi La
tér
ale
Side w
all / P
ar
oi La
tér
ale
Back w
all / A
rr
ièr
e M
ur
Ceiling / Plafond
Floor Protector / Protection de Plancher
K
H
L
J
M
M
C
B
A
E
E
D
D
F
G
Dimension
Inch mm
A Backwall to Stove
11
280
B
Sidewall to Stove
7
178
C Sidewall to Flue
17.3 440
D Wall to Stove (Angled
Installation)
3
77
E
Wall to Flue (Angled Installation) 14.4 366
F
Ceiling Height
84
2134
G Backwall to Flue
14.8 376
SAFETY NOTICE
• If this stove is not properly installed, a house fire may result. To reduce the risk of fire, follow the installation
instructions.
• Consult your municipal building department or fire officials about permits, restrictions and installations
requirements in your area.
•
Use smoke detectors in the room where your stove is installed.
•
Smoke expelled from the unit, by either paint curing, opening the fuel loading door, or a negative pressure
inside the home, could trigger the smoke detectors. Mount smoke detectors at least 10’ from stove
• Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or
“freshen up” a fire in this heater. Keep all such liquids well away from the heater while it is in use.
• In the event of a chimney fire, push the air control full closed to deprive the fire of oxygen. Call the fire
department.
•
A source of fresh air into the room or space heated shall be provided when required.
•
Room heater, solid fuel type, also for use in mobile homes.
•
For Canadian installations, where passage
through a wall, or partition of combustible
construction is desired, the installation must
conform to CAN/CSA-B365.
• A flue pipe crossing a combustible wall
must have a minimum clearance of 18”
(457.2mm).
• To reduce flue clearances from
combustible materials, contact your local
safety department.