Trip Circuit Supervision (TCS)
The trip circuit supervision is use to monitor healthiness of circuit breaker. The trip circuit
extends beyond the relay enclosure and passes through more components, such as fuse,
wires, relay contacts, auxiliary switch contact and so on. The failure of any one of component
result bypassing the protection. The relay is provide with special trip circuit supervision
function which continuously monitor continuity of trip circuit and generate ALARM to take
appropriate action.
The figure 1 represents the logic implementation of Trip Circuit Supervision , It monitors the
continuity of trip circuit through either normally open (CB NO) or normally close (CB NC)
contact of CB connected to Opto isolator digital inputs assigned to CBNO and CBNC
functions. If any discontinuity is observed, then the relay generates TCS Alarm after a time
delay An Alarm message is displayed on LCD display and Event is stored in the Event
Record.
Trip Output Relay
+Ve
-Ve
Circuit Breaker
CBNO
CBNC
R1
R2
S4
S3
Figure 1: Logic Diagram for Trip Circuit Supervision
When the CB is closed, supervision current passes through the Opto-input, into the trip coil
via CBNO. When the CB is open, supervision current flows through the Opto-input and into
the trip coil via the CBNC auxiliary contact. This means that TCS (Trip Coil healthy) signal is
high when the CBNO or CBNC signal is available. Otherwise IED Generates TCS Fail signal
which is used to block the protection function.
Breaker Failure Setting (50BF)
If the Circuit Breaker fails to operate within the settable time following the protection trip then
relay generates a circuit breaker failure trip signal. Following the inception of a fault one or
more main protection devices will operate. Operation of the circuit breaker is essential to
isolate the fault, and prevent damage or further damage to the power system.
For transmission and sub-transmission systems, slow fault clearance can also threaten
system stability. It is therefore common practice to install circuit breaker failure protection
Содержание ADR241B
Страница 10: ...Page intentionally Left Blank...
Страница 20: ...Page intentionally Left Blank...
Страница 34: ...Page intentionally Left Blank...
Страница 50: ...Page intentionally Left Blank...
Страница 87: ...Page intentionally Left Blank...
Страница 111: ...Page intentionally Left Blank...
Страница 112: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM MS Rev No 06 Page No 112 of 272 Section 5 Metering Section...
Страница 115: ...Page intentionally Left Blank...
Страница 116: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM SS Rev No 06 Page No 116 of 272 Section 6 Setting Sheet...
Страница 129: ...Page intentionally Left Blank...
Страница 130: ...Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM CS Rev No 06 Page No 130 of 272 ADR241B Section 7 Communication...
Страница 145: ...Page intentionally Left Blank...
Страница 146: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM UG Rev No 06 Page No 146 of 272 Section 8 User Guide...
Страница 217: ...Page intentionally Left Blank...
Страница 218: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM FC Rev No 06 Page No 218 of 272 Section 9 Flow Chart...
Страница 255: ...Page intentionally Left Blank...
Страница 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Страница 262: ...Page intentionally Left Blank...
Страница 263: ...Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM TC Rev No 06 Page No 263 of 272 ADR241B Section 11 Testing and Commissioning...