Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/TC
Rev No.
: 06
Page No. : 267 of 272
ADR241B
Post instillation / Commissioning observation
After successful installation confirm amount of existing load current in each phase (A, B, and
C) and Earth Fault (EF). This can be confirmed with Analogue/ Digital current meter available
on panel with relay primary and secondary current measurement window. In normal
balanced load condition, the i.e. current should be very low.
11.4
Relay Testing
Relay Calibration & Measurement
Before conducting actual test, confirm relay calibration by following method.
•
Connect ADR241B relay to current injector and timer.
•
Following chart shows terminal numbers of connections.
Source Terminal
Relay Terminal
Relay Connection
Current Source
A1 – A2
Current A-CT _1A
A3 – A4
Current A-CT _5A
A5 – A6
Current B-CT _1A
A7 – A8
Current B-CT _5A
A9 – A10
Current C-CT _1A
A11 – A12
Current C-CT _5A
A13 – A14
Current EF-CT _1A
A15 – A16
Current EF-CT _5A
Power Supply (+ / -)
C1 – C2
Power Supply (+ / -)
Earth
C3
Earth Terminal
Logic Input
B1 – B2
Opto I/P-In1
B1 – B3
Opto I/P-In2
B1 – B4
Opto I/P-In3
B1 – B5
Opto I/P-In4
B1 – B6
Opto I/P-In5
B1 – B7
Opto I/P-In6
C4 – C5
Opto I/P-In7
C6 – C7
Opto I/P-In8
Logic Output
C8 – C9
OUT 1
C10 – C11
OUT 2
C12 – C13 – C14
OUT 3
C15 – C16 – C17
OUT 4
B8 – B9
OUT 5
B10 – B11
OUT 6
B12 – B13
OUT 7
B14 – B15
OUT 8
Содержание ADR241B
Страница 10: ...Page intentionally Left Blank...
Страница 20: ...Page intentionally Left Blank...
Страница 34: ...Page intentionally Left Blank...
Страница 50: ...Page intentionally Left Blank...
Страница 87: ...Page intentionally Left Blank...
Страница 111: ...Page intentionally Left Blank...
Страница 112: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM MS Rev No 06 Page No 112 of 272 Section 5 Metering Section...
Страница 115: ...Page intentionally Left Blank...
Страница 116: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM SS Rev No 06 Page No 116 of 272 Section 6 Setting Sheet...
Страница 129: ...Page intentionally Left Blank...
Страница 130: ...Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM CS Rev No 06 Page No 130 of 272 ADR241B Section 7 Communication...
Страница 145: ...Page intentionally Left Blank...
Страница 146: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM UG Rev No 06 Page No 146 of 272 Section 8 User Guide...
Страница 217: ...Page intentionally Left Blank...
Страница 218: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM FC Rev No 06 Page No 218 of 272 Section 9 Flow Chart...
Страница 255: ...Page intentionally Left Blank...
Страница 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Страница 262: ...Page intentionally Left Blank...
Страница 263: ...Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM TC Rev No 06 Page No 263 of 272 ADR241B Section 11 Testing and Commissioning...