AW-D316 Conventional Sounder Beacon 

User Manual 

I. Overview 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

AW-D316 Conventional Sounder Beacon can give audible 
and visual alarms after being connected to a DC24V 
power supply. It can be used with a bus-type fire alarm 
control panel through an output module. After receiving a 
start command given by the fire alarm control panel 
following an accident, the output module will start the 
Sounder Beacon. After that, the Sounder Beacon will give 
a dazzling visual alarm signal and a harsh audible alarm 
signal to remind the persons on the scene of the accident 
of the fact that a fire has occurred on the site quickly and 
the necessity to take related evacuation measures, thus 
preventing the fire accident from becoming a major one. 
The Sounder Beacon may be used to give audible alarms 
and visual alarms at the scenes of accidents.It is 
applicable to places like high-rise residential buildings, 
public places, hotels, amusement buildings,factories, 
shopping centers, hospitals, schools, office buildings and 
stock exchanges, and particularly to the places with a low 
visibility or the possibility of generation of smoke. 

 

II. Product features 

 

Meet both EN54-3 and EN54-23 

 

Designed with an upper cover and a lower cover 

and  installed on an independent base, it can be 
installed, 

debugged 

and 

maintained 

conveniently.   

 

Suitable for wall and ceiling mount application   

 

Providing 16 tones.   

 

Highly  efficient  LED  technology  and  specially 

designed lens 

 

Light output synchronization. 

 

III.Technical Specification 

1. 

Executive Standard: EN54-3/EN54-23 Type A indoor   

2. 

Operating voltage:DC24V(20V~28V) 

3. 

Operating Current:

100mA@DC24V 

4. 

Sound output:

75dB(A) @ 1m(Tone 1). 

5. 

Number of tones:16     

6. 

EN54-23 coverage:C-3-8/W-2.4-6   

7. 

Flash rate: 0.5Hz 

8. 

Flash color: white 

9. 

Light output synchronization:meets EN54-23 

10.  Protection class: IP21C 
11.  Operating temperature: -10

+55

    Relative 

Humanity:≤95% (non-condensing) 

12.  Material Lens/Body: Flame retardant PC/ABS 

13.  Dimension:

φ

110mm

×

108mm (with    base) ,See 

Fig1. 

14.  Weight:about 266g 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

  Fig.1 

 

V. Tone Setting 
 

 
 
 
 
 
 
 
 
 
 
 
 
                                                  Fig.2 
The tone of the sounder beacon can be set by the 4-way 
DIP  switch,which  is  at  the  back  of  the  main  body(see     
Fig. 2). For more detail, please refer to the Tone Table. 

Note:e.g.

”1,0,0,0”means “Switch 1 is ON, Switch 2~4 are 

OFF

”. 

 
 
 
 
 

Tone Table 

Tone 

Switch 

Decription 

0,0,0,0 

[email protected] 

1,0,0,0 

970Hz 

0,1,0,0 

800Hz/970Hz@2Hz 

1,1,0,0 

800Hz-970Hz@1Hz 

0,0,1,0 

970Hz 1s off/ 1s on 

1,0,1,0 

970Hz 0.5s/ 630Hz,0.5s 

0,1,1,0 

500Hz-1200Hz

×

3,3.5s on /0.5s off 

1,1,1,0 

2840Hz,0.5s on/0.5s off

×

3 /1.5s off 

0,0,0,1 

2840Hz,0.4s on,0.3s off 

10 

1,0,0,1 

550Hz,0.7s/1000Hz,0.33s 

11 

0,1,0,1 

1500Hz-2700Hz@3Hz 

12 

1,1,0,1 

2400Hz 

13 

0,0,1,1 

[email protected] 

14 

1,0,1,1 

2400Hz-2900Hz@9Hz 

15 

0,1,1,1 

2400Hz-2900Hz@3Hz 

16 

1,1,1,1 

500Hz-1200Hz,3.75s on/0.25s off 