15
15
EN
6.3. ROLLING RAMP
• latches automatically in the folded condition
2
6.4. PIPE / CABLE LEADTHROUGH
• prepared on top section
The pipe/cable can now be
fed in without further insulati-
on measures.
CAUTION:
The max. permissible lead-through diameters in accordance with BS EN 14470-2 (10 mm for pipes,
20 mm for cables) are to be observed!
All unused holes in the cabinet wall must be properly sealed with suitable fire protection putty (ROKU
1000, order no. 6520) over the full area and the complete wall thickness.
It is recommendable to manufacture the pipes from rustproof stainless steel or a material with similar
conductive properties in order to maintain the fire resistance characteristics established and specified
during the test.
6.5. ERMETO SCREW CONNECTION
• prepared on top section
• Thanks to the R3/8” internal threads a conventional ermeto screw connection can be mounted
in the second step.
STANDARD
COMFORT